LRC error check(ASCII mode)
The error check in ASCII mode is LRC (Longitudinal Redundancy Check). To calculate the LRC
value: add all the data from ADR to the last one, take the result by using 256 as the unit, and
the excess part is removed(for example, the result obtained after adding is 128H in hexadecimal,
then only 28H is taken), and then calculate complement of 2. The complement is LRC error
value.
For example: read 2 words (word) from the start address 0104h of the servo drive device
number 01h. 01H+03H+01H+04H+00H+02H = 0BH. The complement of 2 is F5H, thus LRC
is ’F’,’5’.
STX
:
ADR
0
1
CMD
0
3
Start Data
Address
0
1
0
4
Data quantity
0
0
0
2
LRC error check
F
5
End1
0DH(CR)
End0
0AH(LF)
End1, End0(communication is completed)
Use “0Dh” which character is ’\r’
『
carriage return
』
and “0Ah” which character is ’\n’
『
new line
』
to denote the end of communication.
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...