46
DO wiring of CN1
DO function allows users to edit parameters by themselves, detail is in the following table.
Signal name
Code
Function
Control
mode
Ready
RD
RD is on when servo is on and ready to
operate.
ALL
Alarm signal output
ALM
ALM is off when power is off or
activating protection circuit makes main
circuit open.
If no alarm occurs, ALM will be on 1
second after power is on.
ALL
In-position ready
INP
INP is on when the servo is in the
setting in-position range. This range
can be adjusted by parameter setting.
When the in-position range setting is
large, the INP may be kept conductive
during low speed operation.
Pr,
Pt
Speed attained
SA
SA is on when servo motor speed is
nearly reached the setting.
The SA keeps on when setting speed is
50r/min or below.
S
Home moving
completion
HOME
Home is on after the completion of
homing moving.
Pr
Torque limiting
control
TLC
When the generated torque reaches the
level set by internal torque limit( PA05)
or analog torque limit( TLA), TLC is on.
TLC turns off when SON is OFF.
Pr,
Pt,
S
Speed limiting
control
VLC
In torque control mode, when the speed
reaches internal speed command 1~7
or analog speed limit(VLA), VLC is on.
VLC turns off when SON is off.
T
Electromagnetic
brake interlock
MBR
If using the motor with electromagnetic
brake, set its parameter to □1□□. MBR
is off when servo is off or alarm occurs.
MBR turns on when servo is ON.
ALL
Warning
WNG
WNG is on when a warning occurs.
WNG is off if no warning occurs.
ALL
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...