449
AL.51 Motor parameter automatic identification error
Alarm cause
Checking method
Corrective action
when the motor is
executing the PL02 Motor
Parameter auto
identification function, this
alarm is triggered if the
friction is too large made
the motor unable to run, or
input values of the
resolution and pole pitch
error.
1. Check if input values of
the resolution and pole
pitch are correct.
2. Check if the motor is
stuck during detection.
3. Check if the friction
between the motor and
mechanical part is too
large.
4. Check if linear scale
feedback is normal,
disconnected, stick
unevenly, or there is noise
interference.
1.Input the actual value
and then executing auto
detection.
2.Due to the linear motor
will move 1 pole pitch
forward or reversely during
detection. You need to
leave the motor moving
distance before detection.
3.Correct the linear scale
problem.
AL.52 Initial magnetic field detection error
Alarm cause
Checking method
Corrective action
When the motor is not using the
Hall sensor, it will automatically
detect the magnetic field after
power-on. If the magnetic field is
not found, this alarm occurs.
1.Check if the feedback is
normal.
2.Check if the motor
friction is too large.
1.Eliminate
feedback error.
2.Increase PL12(the
magnetic detection
current).
AL.53 Motor parameters are not confirmed
Alarm cause
Checking method
Corrective action
When PL03=0, if the motor is
SERVO ON, the alarm occurs.
Check PL03.
Check if motor
parameters is correct,
if yes, set PL03=1
and cycling the
power.
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...