138
5.4.
Position mode parameter setting and operation
(1) Apply power to the servo drive
After applying power to the servo drive, please switch off the DI SON signal, the servo drive
display shows “Servo Motor Rotation Speed “ 2 seconds later automatically.
(2) Test operation
Use JOG operation to check if the servo is running normally.
(3) Parameter setting
After wiring for position control mode, you need to set below parameters to perform basic
positioning control function.
Parameter
Name
Setting
value
Content
PA01(Note1)
Control mode option
□□□0
Position mode
PA02(Note2)
Auto tuning
0002
Auto gain mode 1
PA03
Auto-tuning response level
setting
0012
Middle response
PA06
Electronic gear numerator
1
Set the numerator as 1
PA07
Electronic gear denominator
1
Set the denominator as
1
PA13
Command pulse option
Refer to section 8. 3 parameter
description
PD15(Note
1)
Digital input filter time
□□□2
Filter time constant is
4ms
Note 1: cycle the power to activate the parameter setting.
Note 2: the parameter cannot be set when SON-SG is short-circuited.
(4) Servo ON.
Below is the procedure to execute SERVO ON.
(a)
Apply control power to servo motor.
(b)
Turn on the servo on signal(SON) (SON-SG is short-circuited).
Servo is ready to run when SON is ON, and servo motor switches to SERVO LOCK
immediately.
(c)
When motor is stopped, AL.13 occurs if both LSP and LSN are OFF.
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...