AL.63 The writing parameter value using PR is out of range.
Alarm cause
Checking method
Corrective action
The writing parameter value of PR
command(TYPE=8) is out of
range.
Check whether the writing
parameter value is out of
range when writing the
parameter by PR
procedure.
Clear the alarm by
any of the following
solutions:
1.
Restart the
power.
2.
Press the "SET"
button at alarm
display screen.
3.
Turn on the RES
signal.
AL.64 The writing parameter using PR is wrong.
Alarm cause
Checking method
Corrective action
The PR program(TYPE=8) writes
the parameter during Servo ON.
The servo is on or setting
value is unreasonable
when writing the
parameter by PR
procedure
Adjust PR
commands and
parameters
AL.67 Motor temperature warning
Alarm cause
Checking method
Corrective action
The motor temperature is too high. Check the temperature of
motor.
The alarm will be
released
automatically after
the motor
temperature return
to normal.
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...