162
When you set PA02 to 0000 or 0001, its mainly effective gain value are speed loop gain (PB08),
speed integral gain (PB09), and speed feed-forward gain (PB10). When PA02 is set to 0001,
the interference compensator function will be automatically enabled, which can reduce torque
ripple, overshoot and speed change rate. It is applicable in systems with frequently load
changes, but it cannot be used in a system with an over 10 times load inertia ratio. The gain
value also need to be adjusted according to the situation during operation. The diagram is as
below:
Parameters used in manual mode:
Speed loop gain
Increasing the speed loop gain value will improve the bandwidth. but if the setting is too large,
it will cause the system vibration. It is recommended to estimate a base value in the automatic
mode, and then manually increase the value slowly until the system vibrates if necessary. Set
back the value before system vibrates.
Speed integral gain
Decreasing the value of this parameter will increase the low-frequency stiffness of the speed
loop and reduce the steady-state error. But setting too low may worsen the phase lag, and
may cause system instability.
Speed feed-forward gain
The speed feed-forward gain can reduce the phase lag error and increase the ability of
traceability. When the setting value is close to 100, the dynamic tracking error will be very
small, and the pre-compensation will be the most completed. If the setting is too low, the
improvement effect of the system is small. If the setting value is too large, the system will
easily vibrate.
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...