434
AL.02 Under voltage
Alarm cause
Checking method
Corrective action
The input voltage of
the main circuit is
lower than the
allowable rated value.
Check if the input voltage wiring
for the main circuit is normal.
Recheck the voltage
wiring.
No voltage input to the
main circuit.
Use a voltmeter to check if the
voltage of the main circuit is
normal
Recheck the voltage
switch.
Incorrect power input
(incorrect power
system).
Use a voltmeter to check if the
power system complies with the
specifications.
Use the correct voltage
source or connect to the
voltage regulator in series.
AL.03 Over-current
Alarm cause
Checking method
Corrective action
Motor wiring error.
Check the wire connection
sequence between the motor and
the servo drive.
Followed the wiring
sequence as described in
this manual.
The servo drive output
is short-circuited.
Check the connection between
the motor and servo drive and
make sure that the wire is not
short-circuited.
Check and make sure that
the wire is not short-
circuited. Do not expose
the metal part of the
wiring.
IGBT abnormal.
Check if the temperature of the
heat sink is abnormal.
Send your servo drive
back to the distributor or
manufacturer.
Parameter setting is in
error.
Check if the setting value of the
parameter is much greater than
the default.
Reset the parameter to
the factory default setting
and then modify the
setting gradually.
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...