193
resistor, below is the instruction of selecting the external regenerative resistor capacity:
(a) Without external load
If the motor is running forwardly and reversely, the regenerated energy from brake will first
enter the capacitor of the DC bus. When the voltage of the capacitor exceeds a certain value,
the regenerative resistor will consume the excess recharge energy. The selection method of
regenerative resistor is as follows; The following table provides the calculation of regenerative
energy. Users can refer to below table and calculate the required regenerative resistance.
Drive(W)
Motor
Motor
inertia J
(x10
-4
kg
‧
m
2
)
Es(joule)
(Note 1)
Capacitor
regenerative
energy
Ec(joule)
Maximum
motor
speed.
(rpm)
low inertia
100
SME-L00530○□□□
0.030
0.15
8.1
3000
SME-L01030○□□□
0.052
0.28
8.1
3000
200
SME-L02030○□□□
0.161
0.79
8.1
3000
400
SME-L04030○□□□
0.27
1.37
9.9
3000
750
SME-L07530○□□□
1.07
5.28
16.8
3000
1K
SME-L10020○□□□
6.1
13.38
16.8
2000
1.5K
SME-L15020○□□□
8.8
19.30
40.8
2000
2K
SME-L20020○□□□
11.5
25.22
40.8
2000
3K
SME-L30020○□□□
16.7
36.63
40.8
2000
Middle
inertia
1K
SME-M10020○□□□
10.3
22.59
16.8
2000
1.5K
SME-M15020○□□□
15.0
32.90
40.8
2000
2K
SME-M20020○□□□
32.1
70.4
40.8
2000
3K
SME-M30020○□□□
61.2
134.23
40.8
2000
High inertia
200
SME-H02030○□□□
0.35
1.73
8.1
3000
400
SME-H04030○□□□
0.62
3.06
9.9
3000
750
SME-H07530○□□□
1.66
8.19
16.8
3000
1K
SME-H08515○□□□
13.1
16.05
16.8
1500
3K
SME-H13015○□□□
19.82
24.45
40.8
1500
3K
SME-H18015○□□□
26.42
32.59
40.8
1500
High
inertia(400V
2K
SMP-H18015○□□□
26.1
26.1
134.4
1500
3K
SMP-H29015○□□□
46
46
163.2
1500
5K
SMP-H44015○□□□
67.5
67.5
196.8
1500
5K
SMP-H55015○□□□
89
89
196.8
1500
7K
SMP-H75015○□□□
125
125
240
1500
Содержание SDP Series
Страница 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Страница 42: ...29 2 CN1 connector male Front view Side view Rear view CN1 wiring terminal on the back of CN1 1 26 50 25 ...
Страница 45: ...32 4 The last step is to fasten the screw of housing ...
Страница 203: ...190 It is recommended that the user performs torque position mode switching after motor is stopped completely ...
Страница 385: ...372 ...
Страница 405: ...392 ...
Страница 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Страница 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Страница 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Страница 541: ...528 Middle inertia power cable Middle inertia 2KW 3KW 400V High inertia power cable 1 8KW 2 9KW 4 4KW 5 5KW 7 5KW ...
Страница 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...