3. SIGNALS AND WIRING
3 - 12
(2) Cable connection procedure
(a) Cable making
Refer to table 3.1 for stripped length of cable insulator. The appropriate stripped length of cables
depends on their type, etc. Set the length considering their status.
Insulator
Core
Stripped length
Twist strands slightly and straighten them as follows.
Loose and bent strands
Twist and straighten
the strands.
You can also use a ferrule to connect with the connectors. When you use a ferrule, use the following
ferrules and crimp terminal.
Wire size
Ferrule model (Phoenix contact)
Crimping tool
(Phoenix contact)
For 1 wire
For 2 wires
AWG 16
AI1.5-10BK
AI-TWIN2×1.5-10BK
CRIMPFOX-ZA3
AWG 14
AI2.5-10BU
(b) Inserting wire
Insert only one wire or ferrule to each wire insertion hole.
Insert the open tool as follows and push it down to open the spring. While the open tool is pushed
down, insert the stripped wire into the wire insertion hole. Check the wire insertion depth, and make
sure that the cable insulator will not be caught by the spring and that the conductive part of the
stripped wire will not be exposed.
Release the open tool to fix the wire. Pull the wire lightly to confirm that the wire is surely connected.
In addition, make sure that no conductor wire sticks out of the connector.
The following shows a connection example of the CNP1 connector.
Содержание MR-J4W2-0303B6
Страница 17: ...8 App 16 Status of general purpose AC servo products for compliance with the China RoHS directive App 58 ...
Страница 39: ...2 INSTALLATION 2 8 MEMO ...
Страница 97: ...4 STARTUP 4 20 MEMO ...
Страница 181: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Страница 235: ...9 DIMENSIONS 9 6 MEMO ...
Страница 245: ...10 CHARACTERISTICS 10 10 MEMO ...
Страница 309: ...13 USING STO FUNCTION 13 14 MEMO ...
Страница 365: ...15 USING A DIRECT DRIVE MOTOR 15 24 MEMO ...
Страница 389: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Страница 461: ...17 APPLICATION OF FUNCTIONS 17 72 MEMO ...
Страница 556: ...APPENDIX App 41 ...
Страница 585: ...MEMO ...