15. USING A DIRECT DRIVE MOTOR
15 - 14
2) Specify the setting value that is an approximately 70% of the value set when [AL. 50 Overload 1],
[AL. 51 Overload 2], [AL. E1 Overload warning 1], and [AL. EC Overload warning 2] occurred as
the final setting value. However, if [AL. 27 Initial magnetic pole detection error] occurs with this
value, specify a value intermediate between the value set at [AL. 50 Overload 1], [AL. 51
Overload 2], [AL. E1 Overload warning 1], or [AL. EC Overload warning 2] and the value set at
the magnetic pole detection alarm as the final setting value.
3) Perform the magnetic pole detection again with the final setting value.
(c) Setting example
Existent
Non-existent
Alarm
Magnetic pole detection
[Pr. PL09] setting value
An alarm has occurred when the setting
value of [Pr. PL09] is set to "70".
While increasing the setting value of [Pr. PL09], carry out the
magnetic pole detection repeatedly.
30
35
40
45
65
70
In this example, the final setting value of [Pr. PL09] is 49 (Setting value at the alarm occurrence = 70
× 0.7).
Содержание MR-J4W2-0303B6
Страница 17: ...8 App 16 Status of general purpose AC servo products for compliance with the China RoHS directive App 58 ...
Страница 39: ...2 INSTALLATION 2 8 MEMO ...
Страница 97: ...4 STARTUP 4 20 MEMO ...
Страница 181: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Страница 235: ...9 DIMENSIONS 9 6 MEMO ...
Страница 245: ...10 CHARACTERISTICS 10 10 MEMO ...
Страница 309: ...13 USING STO FUNCTION 13 14 MEMO ...
Страница 365: ...15 USING A DIRECT DRIVE MOTOR 15 24 MEMO ...
Страница 389: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Страница 461: ...17 APPLICATION OF FUNCTIONS 17 72 MEMO ...
Страница 556: ...APPENDIX App 41 ...
Страница 585: ...MEMO ...