5. PARAMETERS
5 - 51
No.
Symbol
Name and function
Initial
value
[unit]
Setting
range
Each/
Common
PF18 **STOD STO
diagnosis
error detection time
Set the time from when an error occurs in the STO input signal or STO circuit until the
detection of [AL. 68.1 Mismatched STO signal error].
When 0 s is set, the detection of [AL. 68.1 Mismatched STO signal error] is not
performed.
The following shows safety levels at the time of parameter setting.
0
[s]
0 to
60
Common
Setting
value
STO input diagnosis by
TOFB output
Safety level
0
Execute
EN ISO 13849-1 Category 3 PL d, IEC
61508 SIL 2, and EN 62061 SIL CL2
Not
execute
1 to 60
Execute
EN ISO 13849-1 Category 3 PL e, IEC
61508 SIL 3, and EN 62061 SIL CL3
Not execute
EN ISO 13849-1 Category 3 PL d, IEC
61508 SIL 2, and EN 62061 SIL CL2
When the short-circuit connector is connected to the CN8 connector, set "0" in the
parameter.
This parameter is available with servo amplifiers with software version C1 or later.
PF21
DRT
Drive recorder switching time setting
Set a drive recorder switching time.
When a USB communication is cut during using a graph function, the function will be
changed to the drive recorder function after the setting time of this parameter.
When a value from "1" to "32767" is set, it will switch after the setting value.
However, when "0" is set, it will switch after 600 seconds.
When "-1" is set, the drive recorder function is disabled.
0
[s]
-1 to
32767
Common
PF23
OSCL1 Vibration tough drive - Oscillation detection level
Set a filter readjustment sensitivity of [Pr. PB13 Machine resonance suppression filter
1] and [Pr. PB15 Machine resonance suppression filter 2] while the vibration tough
drive is enabled.
However, setting "0" will be 50%.
Example: When you set "50" to the parameter, the filter will be readjusted at the time
of 50% or more oscillation level.
50
[%]
0 to
100
Each
PF24 *OSCL2 Vibration tough drive function selection
Refer to Name
and function
column.
Each
Setting
digit
Explanation
Initial
value
_ _ _ x
Oscillation detection alarm selection
0: [AL. 54 Oscillation detection] will occur at oscillation
detection.
1: [AL. F3.1 Oscillation detection warning] will occur at
oscillation detection.
2: Oscillation detection function disabled
Select alarm or warning when a oscillation continues at a
filter readjustment sensitivity level of [Pr. PF23].
The digit is continuously enabled regardless of the vibration
tough drive in [Pr. PA20].
0h
_ _ x _
For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
Содержание MR-J4W2-0303B6
Страница 17: ...8 App 16 Status of general purpose AC servo products for compliance with the China RoHS directive App 58 ...
Страница 39: ...2 INSTALLATION 2 8 MEMO ...
Страница 97: ...4 STARTUP 4 20 MEMO ...
Страница 181: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Страница 235: ...9 DIMENSIONS 9 6 MEMO ...
Страница 245: ...10 CHARACTERISTICS 10 10 MEMO ...
Страница 309: ...13 USING STO FUNCTION 13 14 MEMO ...
Страница 365: ...15 USING A DIRECT DRIVE MOTOR 15 24 MEMO ...
Страница 389: ...16 FULLY CLOSED LOOP SYSTEM 16 24 MEMO ...
Страница 461: ...17 APPLICATION OF FUNCTIONS 17 72 MEMO ...
Страница 556: ...APPENDIX App 41 ...
Страница 585: ...MEMO ...