Chapter 1 Built-in FEnet communication
1-49
Buil
t-
in
Comm
Buil
t-
in
The below table shows the available driver types for the built-in FEnet interface and the descriptions
Items
Descriptions
P2P
Driver
User defined frame
It is the protocol defined by a user for communication with the
opposing device.
XGT client
XGT dedicated protocol.
(No user-defined frame)
Modbus TCP client
Defines the operations with MODICON’s Modbus TCP protocols.
TCP/UDP
You can select between the TCP/UDP.
If you select the Modbus TCP, it will be fixed as TCP.
Client/Server
You can select between the Client/Server.
If you select the XGT dedicated protocol OR Modbus TCP, it will
be fixed as Client.
Partner Port
You can input the opposing device’s port number.
It is the user-defined frame so when defining the protocols, the
random port is designated and you can set the ports at the range
of H400~H1024. However, the XGT dedicated protocol is fixed as
2004 and the TCP is fixed as 502.
Partner IP Address
You can input the opposing device’s IP address.
If you choose the XGT client or Modbus TCP client for the P2P Driver, you cannot apply the user-
defined frame
Notice
(1) Opposing station’s IP address
In case XGT is client, make sure to set the server device’s IP address. If the server is dynamically
allocated the IP through DHCP, the IP address may be changed so you need to check the IP
address before use.
.
3) How to use the Modbus Driver
The below table shows the commands and addresses of the Modbus devices.
Code
Names of function codes
Modicon PLC’s
data address
Remarks
01
Read output contact status (Read Coil Status)
0XXXX (bit-output)
Bit Read
02
Read input contact status(Read Input Status)
1XXXX (bit-input)
Bit Read
03
Read output register (Read Holding Registers)
4XXXX (word-output)
Word Read
04
Read input register (Read Input Registers)
3XXXX (word-input)
Word Read
05
Write output contact 1 bit (Force Single Coil)
0XXXX (bit-output)
Bit Write
06
Write output register 1 word (Preset Single Register)
4XXXX (word-output)
Word Write
15
Sequential Write output contact(Force Multiple Coils)
0XXXX (bit-output)
Bit Write
16
Sequential Write output register
(Preset Multiple Register)
4XXXX (word-output)
Word Write
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...