Chapter 9 Positioning Error Information & Solutions
9-
3
Error
Code
Error Description
Solutions
158
Even the operation pattern set continuous,
current command cannot support continuous
current command.
Continuous operation only can be operated when it is shortening
position control, linear interpolation, and circular interpolation. In
other commands, set operation option to end or continuous.
159
Goal position of operation data exceeds the
range.
For positioning control operating change goal position more than
2,147,483,648 and less than 2,147,483,647.
160
You can not run continuous operation when the
continuous operation bit is disabled.
Check if continuous operation parameter is enabled.
(7) Error Information of Data Writing
Error
Code
Error Description
Solutions
171
Parameter writing command cannot be done
because of start command execution while XG-PM is
sending common parameter
Once current operation is done, eliminate error with error-reset
command, then execute writing command again. Do not execute
start operation while parameter sending.
172
Parameter writing command cannot be done
because of start command execution while XG-PM is
sending operating parameter.
Once current operation is done, eliminate error with error-reset
command, then execute writing command again. Do not execute
start operation while parameter sending.
173
Parameter writing command cannot be done
because of start command execution while
XG-PM is sending operating data.
Once current operation is done, eliminate error with error-reset
command, then execute writing command again. Do not execute
start operation while operating data sending.
174
Parameter writing command cannot be done
because of start command execution while XG-PM is
sending CAM data.
Once current operation is done, eliminate error with error-reset
command, then execute writing command again. Do not execute
start operation while CAM data sending.
175
Start command cannot be executed while writing
sending-parameters or operating-data from XG-PM.
Execute again once writing of parameter or operating data are
done.
(8) Error Information of Positioning command and Step control
Error
Code
Error Description
Solutions
201
Not possible to carry out Homing command in the
state of in operation.
Check if command axis is in operation when the Homing command
is executed.
203
Not possible to carry out Homing command in the
state of Servo Ready OFF.
Check if Driver Ready signal of command axis is OFF when
Homing command is executed.
211
Not possible to carry out Floating origin setting
command in the state of in operation.
Check if command axis is in operation when Floating origin setting
command is executed.
212
Not possible to carry out Floating origin setting
command in the state of Servo Ready OFF.
Check if Driver Ready signal of command axis is OFF when
Floating origin setting command is executed.
221
Not possible to carry out Direct Start command in the
state of in operation.
Check if command axis is in operation whenDirect Start command is
executed.
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...