B
a
s
ic
Chapter 5 Data Log Function
5-14
5.3.3 Data Save Condition
The data log function classifies the data save conditions and intervals as follows, depending on the parameter setting.
(1) Regular Save
The following are condition setting items for Regular Save.
Setting
Operation
Note
Save at every scan
Data are saved after End of each scan
Save at certain interval
Data are saved after End of each scan after lapse of set time
1) Save at every scan
When using the scan interval save method, data are collected after END of each scan. If the volume of stored data is
large, a scan watchdog timer error may occur. Please be mindful of the scan watchdog setting of the basic
parameter. Collecting data exceeding 4 words/10ms or fast save time may cause data loss.
2) Designation Cycle Save
Save data when a set interval arrives. An interval faster than the parameter set the same as the Scan Save may
cause data loss.
Note
(1) Although data collection is performed at the interval set by the parameter, file save into the SD memory is
performed by scan END.
(2) Each group has its buffer area, where certain data are collected an then saved into the SD memory.
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...