Po
sit
io
n
Chap.6 Commands
6-25
6.5 Function blocks related to Start-up and Stop
6.5.1 Homing start-up(XPM_ORG)
Function Block Type
Details
XPM_ORG
DONE
REQ
BASE
SLOT
STAT
BOOL
BOOL
USINT
USINT
UINT
AXIS
USINT
Input
REQ : Request for executing function blocks
BASE : Setting up the numbers of the bases where
modules are equipped
SLOT : Setting up the numbers of slots where modules
are equipped
AXIS : Specifying the axis to give commands
1 ~ 4: 1axis ~ 4axis
Output
DONE : Keeping 1 after the initial operation
STAT : Outputting error No. that occurred during
executing function blocks
(1) It gives homing command to the positioning module.
(2) It is the operation command to find the origin of the machine based on homing mode with direction, compensation
amount, speed(high speed, low speed), address and dwell time that are set as homing parameters of each axis.
(3) The homing command is sent to the axis specified as AXIS of the embedded positioning.
(4) In AXIS, you can set up the axis to command and select one among 1~4. If the values other than set ones are selected,
“error 6” will occur.
(5) When the homing command is normally performed, homing will start up based on the way set in “homing mode” of
“homing parameters”.
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...