6.5 Error Code List
Error
code
(Dec)
Error cause
Action
(restart mode after taking an action)
Operation
status
LED
status
Diagnosis
point
23
Program to execute is
abnormal
Start after reloading the program
Warning
0.5 second
Flicker
RUN mode
24
I/O parameter error
Start after reloading I/O parameter,
Battery change if battery has a problem.
Check the preservation status after I/O parameter
reloading and if error occurs, change the unit.
Warning
0.5 second
Flicker
Reset
RUN mode
switching
25
Basic parameter error
Start after reloading Basic parameter,
Change battery if it has a problem.
Check the preservation status after Basic
parameter reloading and if error occurs, change
the unit.
Warning
0.5 second
Flicker
Reset
RUN mode
switching
26
Compile error exceed
Reduce the program and down.
Heavy
error
0.1
second
Flicker
RUN
mode
switching
27
Compile error
Check the program
Heavy error
0.1 second
Flicker
RUN
mode
switching
30
Module set in parameter
and the installed module
does not match
modify the module or parameter and then restart.
Warning
0.5 second
Flicker
RUN mode
switching
31
Module falling during
operation or additional
setup
After checking the position of
attachment/detachment of expansion module
during Run mode
Warning
0.1 second
Flicker
Every scan
33
Data of I/O module does
not access normally during
operation.
After checking the position of slot where the
access error occurs by XG5000, change the
module and restar (acc.to parameter.)
Heavy error
0.1 second
Flicker
Scan end
34
Normal access of
special/link module
data during operation not
available
After checking the position of slot that access error
occurred by XG5000, change the module and
restart (acc.to parameter).
Heavy error
0.1 second
Flicker
Scan end
38
Extension
Module exceed
Extension module is attached over 10 slot or
communication module is attached over 3 slot
Heavy error
0.1 second
Flicker
RUN
mode
switching
39
Abnormal stop of
CPU or malfunction
Abnormal system end by noise or hard ware error.
1) If it occurs repeatedly when power
reinput, request service center
2) Noise measures
Heavy error
0.1 second
Flicker
Ordinary
time
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...