M
ain
Chapter 2 CPU Function
2-20
2.9 How to allocate I/O No.
Allocation of I/O No. is to allocate the address to each module’s I/O terminals to read the data from the input modules and
output the data in the output modules when executing operation. In the XGB PLC, all modules occupy 64 points.
(1) Allocation of I/O No.
The basic unit occupies 2 slots of No.1 so 124 points are allocated and all remaining expansion module occupies
64 points. (including special, communication modules)
Example of allocating I/O No. based on the system configuration
Slot No.
Model
I/O allocation
Remakrs
0
XEC-DN32U
input : %IX0.0.0 ~ %IX0.0.63
output : %QX0.0.0 ~ %QX0.0.63
Actua linput : %IX0.0.0 ~ %IX0.0.15
Actual output : %QX0.0.0 ~ %QX0.0.15
1
Embedded special
functions
input : %IX0.1.0 ~ %IX0.1.63
output : %QX0.1.0 ~ %QX0.1.63
-
2
XBE-DC32A
input : %IX0.2.0 ~ %IX0.2.63
output : %QX0.2.0 ~ %QX0.2.63
Actual input : %IX0.2.0 ~ %IX0.2.31
3
XBE-TN32A
input : %IX0.3.0 ~ %IX0.3.63
output : %QX0.3.0 ~ %QX0.3.63
Actual output : %QX0.3.0 ~ %QX0.3.31
4
XBL-C21A
input : %IX0.4.0 ~ %IX0.4.63
output : %QX0.4.0 ~ %QX0.4.63
-
5
XBF-AD04A
input : %IX0.5.0 ~ %IX0.5.63
output : %QX0.5.0 ~ %QX0.5.63
-
6
XBF-DV04A
input : %IX0.6.0 ~ %IX0.6.63
output : %QX0.6.0 ~ %QX0.6.63
-
7
XBE-DC16A
input : %IX0.7.0 ~ %IX0.7.63
output : %QX0.7.0 ~ %QX0.7.63
Actual input : %IX0.7.0 ~ %IX0.7.15
8
XBE-RY16A
input : %IX0.8.0 ~ %IX0.8.63
output : %QX0.8.0 ~ %QX0.8.63
Actual output : %QX0.8.0 ~ %QX0.8.15
* The number of empty I/O points can be used as the internal relay.
* In the case of the high performance XGB basic type, it does not have the embedded special function corresponding to No.1
slot but occupies No.1 slot as an empty slot.
(2) When the I/O of the I/O parameter is allocated, the allocation information is displayed.
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...