Chapter 4 Positioning Parameter & Operation Data
4-30
4.8.2 Operation Data Setting
(1) Step No
(a) The setting range of positioning data as serial no. is 0
∼
400.
(b) The first Starting step of operation data is no.1 step.
Notes
In case of designating step number as ‘0’ with indirect start, Simultaneous start, Position synchronous start, it means
current operation step.
(2) Coordinate
(a) Coordinate of position data includes absolute coordinate and incremental coordinate.
1) Absolute Method
a) This carries out the positioning control from the current position to the goal position
(the goal position assigned by positioning data).
b) Positioning is carried out based on the assigned position of homing (origin address).
c) Transfer direction shall be determined by the current position and goal position.
▶
Start position < Goal position : forward direction positioning
▶
Start position > Goal position : reverse direction positioning
[Example]
■ When current position : 1000 , Goal position : 8000, forward direction transfer amount is 7000(8000-1000).
Notes
Positioning by Absolute method (Absolute coordinate) can start only in the state that the origin is determined.
If starting in the state that the origin is not determined, Error will occur.
2) Incremental method
a) This carries out the positioning control as much as goal transfer amount from the current position.
b) Transfer direction shall be determined by the sign of transfer amount.
.
■ When transfer direction is (+) or no sign : forward direction positioning (position increase direction)
■ When transfer direction is ( - )
: reverse direction positioning (position decrease direction)
1000
Current position
Goal position
0
8000
Transfer amount: 7000
Current position
Transfer direction when transfer amount is (-)
Transfer direction when transfer amount is (+)
Reverse
Forward
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...