Chapter 1 Embedded Analog
1-12
1.5 Embedded Functions
Functions of embedded analog module are as described below.
Function
Description
Channel Run/Stop
setting
● Specify Run/Stop of the channel to execute A/D, D/A conversion.
● If the unused channel is set to Stop, whole Run time can be reduced.
Input / output
voltage/current range
setting
● Specify analog input / output range to be used.
● Select range in parameter setting after selecting Voltage/Current input / output
according to the wiring properly.
● Embedded analog module provides two kinds of current input / output ranges
(4~20mA, 0~20mA) and four kinds of voltage input / output ranges (1~5V, 0~5V,
0~10V,-10~10V)
Input / output data
format setting
● Specify digital input / output type.
● 4 data formats are provided in this module.
(Unsigned value, Signed value, Precise value, Percentile value)
A/D conversion
methods
● Sampling processing
- Sampling process will be performed if A/D conversion type is not specified.
● Filter processing
- Used to delay the sudden change of input value.
● Average processing
- Outputs average A/D conversion value based on time or count.
● Detection alarm (Input disconnection)
- After detecting whether disconnection of the input circuit, the alarm is
displayed by a single flag.
(Input signal range : 4 ~ 20
㎃
, 1 ~ 5 V)
● Maintenance function of valid conversion value.
- When valid conversion value is exceeded, whether conversion value
retains will be able to set.
● Alarm function
- When exceeding valid input range, alarm and maximum /minimum flag
will be generated.
D/A output status setting
● Set the output status of channel when changing 'Run' to 'Stop'.
● The four kinds of output statuses (Previous, Min, Mid, Max value) are provided.
Interpolation method
setting
● Set linear interpolation, S-type interpolation method.
Detecting output
disconnection
● Detection alarm (Output disconnection)
- After detecting whether disconnection of the output circuit, the alarm is
displayed by a single flag.
(Output signal range : 4 ~ 20
㎃
, 0 ~ 20
㎃
)
1.5.1 Sampling Processing
It collects analog input sign through general A/D conversion processing at a specific interval to convert to digital. The time
required for A/D conversion of analog input sign till saved on the memory depends on the number of channels used.
(Processing time) = (Number of channels used) X (Conversion speed)
(i.e.)
If the number of channels used is 3, its process time will be
3 x 0.5
㎳
= 1.5
㎳
Sampling is to calculate the sampling value of continuous analog sign at a specific interval.
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...