B
asi
s
Chapter 6 Built-in PID Function
6-34
(2) Auto-tuning flag function
Each function of K area flags for XGB series auto-tuning is summarized as follows.
A) Common bit area
The area is a flag collecting operation setting and information consisting of bits to each 16 loop. Each bit of each word
device represents the information of each loop.
1) _AT_REV (auto-tuning run direction setting)
It determines the run direction of auto-tuning of ‘n’ th loop. If the bit is off, it is forward operation; if on, it is reverse operation.
2) _AT_PWM_EN (PWM output enable)
It sets whether to output the auto-tuning MV of ‘n’ th loop as PWM output. If the bit is off, it is disabled; if on, it is enabled.
3) _AT_ERROR (Auto-tuning error occurrence)
It indicates the error in case an error that discontinues operation during auto-tuning of ‘n’th loop occurs. If an error occurs,
it is on; if normal, it is off. Once an error occurs, auto-tuning stops and the MV is output as the min. output set in the
parameter. Also, if an error occurs, it indicates the error code in the error code area of a loop. For more information about
error code types and measures, refer to 6.5. The area, as a dedicated monitor area, is updated although a user directly
enters it.
B) Auto-tuning flag area by loops
The auto-tuning flag areas by loops are K1860 ~ K2179 and each 20 words per loop are allocated to totally 16 loops.
Therefore, individual data area of ‘n’ th loop is between K (1860+16*n) ~ K (1879+16*n).
1) _ATxx_SV (auto-tuning xx Loop SV setting)
It sets/indicates the auto-tuning SV of ‘xx’th loop.
The available scope is between -32,768 ~ 32,767.
Flag name
Address
IEC type address
Unit
Setting
_AT_REV
(PID RUN direction setting)
K1856n
%K n
BIT
Available
Flag name
Address
IEC type address
Unit
Setting
_AT_PWM_EN
(PWM output enable)
K857n
%K n
BIT
Available
Flag name
Address
IEC type address
Unit
Setting
_PID_ERROR
(PID error occurrence)
K1858n
%K n
BIT
Unavailable
Flag name
Address
IEC type address
Unit
Scope
_ATxx_SV
(AT xx Loop SV setting)
K1860+16*xx
%16*xx
INT
-32,768 ~ 32,767
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...