Chapter 2 Built-in Cnet communication
2-92
B
u
ilt
-in
C
omm
3) Frame monitor
The user can check whether frame is normal or not by monitoring TRX frame through Cnet I/F module by XG-PD’s frame monitor.
Check list
Detail result
Frame
monitor
1. Select [Online] – [Communication module setting] – [System Diagnosis] or click the icon ( ).
2. If you click right button after clinking Cnet I/F module and click frame monitor, you can monitor current
communication data.
3. If you use frame monitor function, you can check frame of TRX data between Cnet I/F module and external
communication device easily.
4. Detailed content of information indicated frame monitor window is as follows.
Item
Content
Remark
Standard
information
Base No.
Information of base number under diagnosis
Slot No.
Information of slot number under diagnosis
Monitor
selections
Select Channel
Select channel to monitor
Frame
monitor
window
Form
Indicates whether it is TX or RX frame.
Result
Indicates the protocol type
1) XGT server
2) XGT client
3) Modbus server
4) Modbus client
5) User definition frame
6) Unknown: frame that Cnet can’t deal with
Size
Size of frame
Time
Time when sending/receiving the frame
In case main unit is standard type (XBM-D***S), it indicates elapsed time
from start.
Frame data
Indicates the frame data
View by HEX
Indicates the frame data as HEX
View by ASCII
Indicates the frame data as ASCII
Start
Starts the frame monitor
Stop
Stops the frame monitor
Close
Closes the frame monitor window
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...