Chapter 1 Configuration and Operation Mode of Programs
1-28
1.3.3 Data retain area setting
In case you want to keep the data necessary for operation and the data made during operation when PLC stops and restarts,
Default(automatic) Variable Retain is used and some area of M area can be set as Retain area through parameter setting
The following is characteristic table about the device available for Retain setting
Device
Retain
setting
Retain
Characteristic
Default
O
Depend
on
setting
As for automatic variable area, Retain setting is available
M
O
As for internal contact point area, Retain setting is available at parameter
K
X
O
In case of power failure, contact point is kept
F
X
X
System flag area
U
X
X
Analog data register (Retain is not available)
L
X
X
High speed link/P2P service status contact point of communication module (Retain is
available)
N
X
O
P2P service address area of communication module (Retain is available)
R
X
O
Flash memory dedicated area (Retain is available)
Remark
1) K, N, R devices are retained basically.
2) K, L, N devices can be deleted through “Clear PLC” of XG5000 online menu.
3) For more detail, refer to “Online” of XG5000 user manual.
(1)Initialization of data according to restart mode
There are three variable related with restart mode (Default, initialization and retain variable). Initialization method about each variable in
case of executing restart mode is as follows.
(2)Operation of data retain area
Method on deleting the Retain data is as follows.
- RESET through XG5000 (Overall Reset)
- Execute “Clear PLC” through XG5000 at STOP mode
- Writing by program (Initialization program recommended)
- Writing ‘0’ FILL etc at XG5000 monitor mode
Mode
Variable assignment
COLD
WARM
Default
Initialized as ‘0’
Initialized as ‘0’
Retain
Initialized as ‘0’
Hold previous value
Initialization
Initialized as user defined value
Initialized as user defined value
Retain & Initialization
Initialized as user defined value
Hold previous value
Содержание XBE-DC08A
Страница 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Страница 155: ...Main Chapter 2 CPU Function 2 29 Notice For more details on the monitor refer to the XG5000 manual ...
Страница 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Страница 512: ...Positioning Chapter 7 Program 7 8 manual operation 7 1 4 Parameter and Operation Data Setting 1 Parameter Setting ...
Страница 644: ...Positioning Chapter 8 Functions 8 91 ...
Страница 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Страница 861: ...Special Chapter 1 Embedded Analog 1 39 5 Select View Variables Comments Variables and comments are both displayed ...
Страница 1206: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 CPU Type XEC DN32U 2 Positioning Type XEC DN32UP ...
Страница 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Страница 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Страница 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...