29
⎯
6 F 2 S 0 8 4 6
is established when the binary input signal (PLC signal) CRT_BLOCK is "0" and the scheme
switch [CRSCM] is set to "ON" as shown in Figure 2.4.1.6.
CRT USE
+
"ON"
[CRSCM]
&
1
CRT_BLOCK
1601
9
Figure 2.4.1.6 Communication Service Logic
The service condition of the external main protection in duplicated scheme is input with the binary
input signal (PLC signal) M-PROT_ON. The command protection in Table 2.4.1.1 is out of
service when both main protections are out of service.
Table 2.4.1.1 Zone 1 Trip Mode Control
Z1CNT COMMAND
PROTECTION
Position
IN SERVICE
OUT OF SERVICE
1
INST. TRIP & AUTO-REC
INST. FINAL TRIP
2
DELAYED FINAL TRIP
INST. FINAL TRIP
3
TRIP BLOCKED
INST. FINAL TRIP
4
INST. TRIP & AUTO-REC
5
INST. FINAL TRIP
The zone 1 tripping mode at each position of the switch [Z1CNT] is as follows:
Position 1: When the command protection is in service, zone 1 executes instantaneous tripping
and starts autoreclose. Zone 1 performs single-phase tripping and reclosing or three-phase tripping
and reclosing depending on the reclose mode of the autoreclose function and the type of faults
(single-phase faults or multi-phase faults). If the autoreclose is out of service, zone 1 performs
instantaneous three-phase final tripping for all faults.
If the command protection is out of service, zone 1 performs instantaneous three-phase final
tripping.
Position 2: Zone 1 performs three-phase tripping with a time delay using timer TZ1 if the
command protection is in service, and it performs three-phase tripping instantaneously if the
command protection is out of service and does not start the autoreclose.
Position 3: Zone 1 tripping is blocked if the command protection is in service, and instantaneous
three-phase tripping is performed if it is out of service. Autoreclose is not started.
Position 4: Zone 1 executes instantaneous tripping irrespective of the command protection
conditions and initiates autoreclose. This instantaneous tripping becomes single-phase tripping or
three-phase tripping depending on the autoreclose mode and type of faults (single-phase faults or
multi-phase faults). If the autoreclose is out of service, zone 1 performs instantaneous three-phase
final tripping.
Position 5: Zone 1 performs instantaneous three-phase final tripping irrespective of the command
protection.
Zone 1 Trip Mode Control is performed using PLC function as shown in Figure 2.4.1.7. By
changing the PLC default setting, the Z1 trip can be controlled independently of the [Z1CNT]
setting.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......