Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
•
Press 3 (= Comm.) on the "Setting (change)" screen to display the "Communication" screen.
/ 2
c
C o m m u n i
n
t
a
o
i
c h
2 = S w i t
e s s
1 = A d d r
t
/ P a r a m e
r
e
•
Press 1 (= Address/Parameter) to enter the relay address number.
/3 Address/Parameter 1/ 15
HDLC ( 1- 32): 1 _
IEC ( 0- 254): 2
SYADJ( -9999- 9999): 0 ms
IP1-1( 0- 254): 0
IP1-2( 0- 254): 0
IP1-3( 0- 254): 0
IP1-4( 0- 254): 0
SM1-1( 0- 254): 0
SM1-2( 0- 254): 0
SM1-3( 0- 254): 0
SM1-4( 0- 254): 0
GW1-1( 0- 254): 0
GW1-2( 0- 254): 0
GW1-3( 0- 254): 0
GW1-4( 0- 254): 0
•
Enter the address number on "HDLC" column for RSM and/or "IEC" column for
IEC60870-5-103 and the compensation value on "SYADJ" column for adjustment of time
synchronization of protocol used. (
−
: lags the time, +: leads the time) And enter IP address for
IP1-1 to IP1-4, Subnet mask for SM1-1 to SM1-4, and Default gateway for GW1-1 to GW1-4.
IP
address:
∗∗∗
,
∗∗∗
,
∗∗∗
,
∗∗∗
IP1-1 IP1-2 IP1-3 IP1-4
Subnet mask SM1-1 to SM1-4 and Default gateway GW1-1 to GW1-4: same as above.
•
Press
the ENTER key.
CAUTION:
Do not overlap the number in a network.
•
Press 2 (= Switch) on the "Communication" screen to select the protocol and transmission
speed (baud rate), etc., of the RSM or IEC60870-5-103.
/3 Switch 1/ *
PRTCL1 1=HDLC 2=IEC103 2 _
232C 1=9.6 2=19.2 3=38.4 4=57.6 4
IECBR 1=9.6 2=19.2 2
IECBLK 1=Normal 2=Blocked 1
•
Select the number corresponding to the system and press the ENTER key.
<PRTCL1>
PRTCL1 is used to select the protocol for channel 1 (COM1 or OP1) of the serial communication
port RS485 or FO (fibre optic).
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......