170
⎯
6 F 2 S 0 8 4 6
4.1.2 Communication Ports
The following 3 individual interfaces are mounted as the communication ports:
•
RS232C
port
•
Serial communication port (RS485 port, optional Fibre optic or Ethernet LAN etc.)
•
IRIG-B
port
(1) RS232C port
This connector is a standard 9-way D-type connector for serial port RS232C transmission and
mounted on the front panel. By connecting with a personal computer using this connector, setting
operation and display functions can be performed on the personal computer.
(2) Serial communication port
One or two serial communication ports can be provided. In the single-port type, it is connected to
the RSM (Relay Setting and Monitoring system) via the protocol converter G1PR2 or
IEC60870-5-103 communication via BCU/RTU (Bay Control Unit / Remote Terminal Unit) to
connect between relays and to construct a network communication system. (See Figure 4.4.1 in
Section 4.4.)
In the case of the two-port type, one port (COM1) can be used for the relay setting and monitoring
(RSM) system or IEC60870-5-103 communication, while the other port (COM2) is used for
IEC60870-5-103 communication only.
Screw terminal for RS485, ST connector for fibre optic or RJ45 connector for Ethernet LAN
(10Base-T) is provided on the back of the relay as shown in Figure 4.1.2.1.
(3) IRIG-B port
The IRIG-B port is mounted on the transformer module. This port collects serial IRIG-B format
data from the external clock to synchronize the relay calendar clock. The IRIG-B port is isolated
from the external circuit by using a photocoupler. A BNC connector is used as the input connector.
This port is provided on the back of the relay and Figure 4.1.2.1 shows the location of this
connector.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......