157
⎯
6 F 2 S 0 8 4 6
The binary input signals of circuit breaker auxiliary contact are transformed as shown in Figure
3.2.1.2 to use in the scheme logic.
&
&
≥
1
CB-AND
&
≥
1
1
&
&
&
CB-OR
CB-DISCR
CB1_CONT-A
1536
CB1_CONT-B
1537
CB1_CONT-C
1538
101
102
BI1_command
BI2_command
BI3_command
[Default setting]
Figure 3.2.1.2 Circuit Breaker Signals Transformation
3.2.2 Binary Output Signals
The number of binary output signals and their output terminals vary depending on the relay
models. For all models, all outputs except the tripping command and relay failure signal can be
configured.
The signals shown in the signal list in Appendix B can be assigned to the output relay individually
or in arbitrary combinations. Signals can be combined using either an AND circuit or OR circuit
with 6 gates each as shown in Figure 3.2.2.1. The output circuit can be configured according to the
setting menu. Appendix D shows the factory default settings.
A 0.2s delayed drop-off timer can be attached to these assigned signals. The delayed drop-off time
is disabled by the scheme switch [BOTD].
The GRZ100 can implement transmission of signals to the remote terminal either by opening or
closing the output contact in response to a request from the telecommunication equipment. The
transmission signal is assigned to BO13 of IO2 by the binary output setting.
The relay failure contact closes the contact when a relay defect or abnormality in the DC power
supply circuit is detected.
Figure 3.2.2.1 Configurable Output
+
"ON"
Signal List
Appendix B
0.2s
t
0
[BOTD]
6 GATES
or
6 GATES
&
≥
1
&
≥
1
Auxiliary relay
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......