⎯
45
⎯
6 F 2 S 0 8 4 6
forward overreaching elements at both terminals. It is possible to use zone 2 or zone 3, as the
forward overreaching element.
The POP is provided with an echo function and weak infeed trip function so that even when the
protection is applied to a line with open terminal or weak infeed terminal, it enables fast tripping of
both terminals for any fault along the whole length of the protected line. An undervoltage element
UVL is provided for weak infeed tripping. (See Section 2.4.3.5 for protection for weak infeed
terminal.)
When a sequential fault clearance occurs for a fault on a parallel line, the direction of the current
on the healthy line is reversed. The status of the forward overreaching element changes from an
operating to a reset state at the terminal where the current is reversed from an inward to an outward
direction, and from a non-operating status to operating status at the other terminal. In this process,
if the operating periods of the forward overreaching element of both terminals overlap, the healthy
line may be tripped erroneously. To prevent this, current reversal logic (CRL) is provided. (See
Section 2.4.3.6 for current reversal.)
Since the POP transmits a trip permission signal with the operation of the overreaching element, it
requires multiplex signaling channels or one channel for each direction. This ensures that the
transmitting terminal does not trip erroneously due to reception of its own transmit signal during
an external fault in the overreaching zone.
Scheme Logic
Figure 2.4.3.2 shows the scheme logic for the POP. The POP transmits a trip permission signal to
the other terminal for any of the following conditions.
•
The forward overreaching zone 2 or zone 3 selected by scheme switch [ZONESEL]
operates and the current reversal logic (CRL) has not picked up. If the PLC signal
PSCM_TCHDEN is established, the delayed pick-up timer TCHD is provided.
•
The circuit breaker is opened and a trip permission signal CR is received from the other
terminal.
•
The forward overreaching zone 2 or zone 3 and reverse looking Z4 have not operated
and a trip permission signal is received from the other terminal.
The last two are implemented when an echo function (ECH) is selected. (Refer to Section 2.4.3.5
for echo function.)
Transmission of the trip permission signal continues for the TSBCT setting even after the local
terminal is tripped by the delayed drop-off timer TSBCT. This is to ensure that command tripping
is executed at the remote terminal.
The POP outputs single-phase tripping signal S-TRIP or three-phase tripping signal M-TRIP to
the local terminal when the trip permission signal R1-CR is received from the remote terminal, the
current reversal logic (CRL) is not picked up and one of the following conditions is established.
•
The forward overreaching element operates.
•
The undervoltage element UVL (UVLS or UVLG) operates and the forward
overreaching and the reverse looking elements do not operate.
The latter is implemented when the weak infeed trip function is selected. (Refer to Section 2.4.3.5
for weak infeed trip function.)
To select the faulted phase reliably, phase selection is performed using the phase selection element
UVC. Phase selection logic is described in Section 2.4.3.7.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......