⎯
131
⎯
6 F 2 S 0 8 4 6
The voltage and synchronism check is performed as shown below according to the [ARC-CB]
settings:
Setting of [ARC-CB]
Voltage and synchronism check
ONE or O1
A voltage and synchronism check is performed using voltages VB and VL1.
O2
A voltage and synchronism check is performed using voltages VL1 and VL2.
L1
Since the logical level of TPARL-SET is 0, a voltage and synchronism check is performed
for the busbar breaker using voltages VB and VL1. Then, the logical level of TPARL-SET
becomes 1 and a voltage and synchronism check is performed for the center breaker
using voltages VL1 and VL2 and a reclosing command is output to the center breaker.
L2
A voltage and synchronism check is performed for the center breaker using voltages VL1
and VL2. Then, the logical level of TPARL-SET becomes 1 and a voltage and synchronism
check is performed for the busbar breaker using voltages VB and VL1.
Note :
"
ONE
" is set only when the relay is applied to one-breaker system. Trip and reclose commands
are output only for CB1(bus CB).
The energizing control for the two circuit breakers can be set by the scheme switch [VCHK] as
follows:
Setting of [VCHK]
Energizing control
LB1
The lead breaker is reclosed under the "live bus and dead line" condition or with
synchronism check, and the follower breaker is reclosed with synchronism check only.
LB2
The leader breaker is reclosed under the "live bus and dead line" condition or with
synchronism check, and the follower breaker is reclosed under the "dead bus and live line"
condition or with synchronism check.
DB
Both breakers are reclosed under the "dead bus and live line" condition or with
synchronism check.
SYN
Both breakers are reclosed with synchronism check only.
OFF
Both breakers are reclosed without voltage and synchronism check.
The scheme switch [ARC-SUC] is used to check the autoreclose succeeds. If all three phase CB
contacts have been closed within TSUC time after ARC shot output, it is judged that the
autoreclose has succeeded (AS). If not, it is judged that the autoreclose has failed (AF), and
becomes the final tripping (FT).
The relay provides the user configurable switch [UARCSW] with three-positions (P1, P2, P3) to
be programmed by using PLC function. Any position can be selected. If this switch is not used for
the PLC setting, it is invalid.
2.6.3 Setting
The setting elements necessary for the autoreclose and their setting ranges are shown in the table
below.
Element
Range
Step Default Remarks
VT
1 - 20000
1
2000
VT ratio for distance protection
VTs1
1 - 20000
1
2000
VT ratio for voltage and synchronism check
TSPR1
0.01 - 10.00 s
0.01 s
0.80 s
Dead time for single - phase autoreclose
TTPR1
0.01 - 100.00 s
0.01 s
0.60 s
Dead time for three - phase autoreclose
TRR
0.01 - 100.00 s
0.01 s
2.00 s
Autoreclose reset time
TEVLV
0.01 - 10.00 s
0.01 s
0.30 s
Dead time reset for evolving fault
TRDY1
5 - 300 s
1 s
60 s
Reclaim time
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......