121
⎯
6 F 2 S 0 8 4 6
2.6.2 Scheme
Logic
2.6.2.1 One-breaker Autoreclose
Figure 2.6.2.1 shows the simplified scheme logic for the single-shot autoreclose. Autoreclose for a
further fault incident is available when the circuit breaker is closed and ready for autoreclose (CB1
READY=1), the autoreclose mode by the switch [ARC-M] or the PLC is set to "SPAR", "TPAR"
or "SPAR & TPAR" and the on-delay timer TRDY1 is picked up. The TRDY1 is used to
determine the reclaim time.
"SPAR", "TPAR", "SPAR & TPAR"
&
+
[ARC-M]
5-300s
t 0
&
52A
52B
52C
CB1_READY
1545
TRIP-A
TRIP-B
TRIP-C
[ARC-EXT]
≥
1
≥
1
≥
1
"ON"
"ON"
≥
1
EXT_TRIP-A
1556
EXT_TRIP-B
1557
EXT_TRIP-C
1558
&
TP
F/F
Single-phase trip
+
[ARC-M]
"SPAR", "SPAR & TPAR"
&
&
0.01-10s
t 0
TRDY1
TSPR1
SPR.L-REQ
1824
"Default =CONSTANT 1"
&
Multi-phase trip
+
[ARC-M]
"TPAR", "SPAR & TPAR"
&
&
0.01-100s
t 0
TTPR1
TPR.L-REQ
1825
"Default =SYN-OP"
&
≥
1
&
Single-phase trip
0.01-10s
t 0
TEVLV
Multi-phase trip
+
[ARC-M]
"TPAR", "SPAR & TPAR"
&
≥
1
0.01-100s
t 0
TRR
≥
1
0.1 - 10s
TW1
0.2s
ARC(*)
MSARC
(*)ARC
(For Leader CB)
(For Leader CB)
FT
≥
1
ARC
(For Leader CB)
(For Leader CB)
(For Leader CB)
M-TRIPA
FT
≥
1
0.1s
Trip when ARC1 READY not operated.
Multi phase trip in SPAR.
ARC1 READY
( To Figure
2.10.2.8. )
CT-DG
&
"OFF"
+
[ARC-DEF]
BUP
ARC_BLOCK
1544
"OFF"
[ARC-BU]
&
"Disable"
+
[ARC-M]
ARC_BLOCK1
1564
≥
1
ARC FAIL
(For Leader CB)
+
[ARC-SUC]
&
"ON"
Figure 2.6.2.1 Autoreclose Scheme Logic
If the autoreclose is ready, the internal tripping signal TRIP-A, B, C or external tripping signal
EXT_TRIP-A, B, C for each phase of the circuit breaker activates the autoreclose. These tripping
signals are output from the command protection, zone 1 extension protection, and specific zone 1
tripping. Whether or not the external trip signals are used to activate the reclosing is selected by
the scheme switch [ARC-EXT].
Once this autoreclose is activated, it is maintained by a flip-flop circuit until one reclosing cycle is
completed.
Autoreclose is not activated in the following conditions.
•
When the tripping is output by the directional earth fault command protection (CT-DG =1)
and the autoreclose selection switch [ARC-DEF] is set to "OFF".
•
When the tripping is performed by the out-of-step protection (OSTT =1), stub fault protection
(STUB=1), switch-onto-fault protection (SOTF =1) breaker failure protection (RETRIP=1) or
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......