193
⎯
6 F 2 S 0 8 4 6
•
When the remote RSM system applied, select 1 (=HDLC). When the IEC60870-5-103
applied, select 2 (=IEC103).
<232C>
This line is to select the RS-232C baud rate when the RSM system applied.
Note:
The default setting of the 232C is 9.6kbps. The 57.6kbps setting, if possible, is recommended to
serve user for comfortable operation. The setting of RSM100 is also set to the same baud rate.
<IECBR>
This line is to select the baud rate when the IEC60870-5-103 system applied.
<IECBLK>
Select 2 (=Blocked) to block the monitor direction in the IEC60870-5-103 communication.
When using the IEC60870-5-103 communication, set to 1 (=Normal).
4.2.6.5 Setting the Recording
To set the recording function as described in Section 4.2.3, do the following:
•
Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
•
Press 4 (= Record) to display the "Record" screen.
R e c o
1 =
r e c o r d
3 = D i s t u r b a n c e
/ 2
r
a u t
F
l
2 = E v e n t
r e c o r d
r e c o r d
4 = A u t o m a t i c
t e s t
i n t e r v a l
d
Setting the fault recording
•
Press 1 (= Fault record) to display the "Fault record" screen.
r e c o r d
r
1 _
1
1 /
/ 3
0 = O f f
a u t
F
l
1 = O n
l o c a t o
a u t
F
l
•
Enter 1 (= On) to record the fault location.
Enter 0 (= Off) not to record the fault location.
•
Press
the ENTER key.
Setting the event recording
•
Press 2 (= Event record) to display the "Event record" screen.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......