Set [WKIT] and [ECHO] to "On" and apply a weak-infeed fault. Check that instantaneous tripping
is performed.
De-energize the binary input BI4 and apply a zone 2 fault. Check that POP tripping does not occur.
Apply a zone 2 fault, and check that binary output relay BO13 operates.
Set the scheme switch [ECHO] to "On".
De-energize the binary inputs BI1, BI2 and BI3 to simulate the breaker being open.
Check that binary output relay BO13 operates when the binary input BI4 is energized.
Apply a zone 4 fault (reverse fault) while the binary inputs BI1, BI2 and BI3 are energized, and
check that the binary output relay BO13 does not operate when the binary input BI4 is energized.
Check that the indications and recordings are correct.
UOP tripping
Set the scheme switch [SCHEME] to "UOP", [WKIT] and [ECHO] to "Off".
De-energize the binary input BI4 to simulate interruption of a trip block signal reception and apply
a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Set [WKIT] and [ECHO] to "On" and apply a weak-infeed fault. Check that instantaneous tripping
is performed.
Energize the binary input BI14 to simulate trip block signal reception and apply a zone 2 fault.
Check that UOP tripping does not occur.
Check that binary output relay BO13 operates in the normal condition.
Apply a zone 2 fault, and check that the BO13 resets.
Set the scheme switch [ECHO] to "On".
De-energize the binary inputs BI1, BI2 and BI3 to simulate the breaker being open.
Check that binary output relay BO13 resets when the binary input BI4 is de-energized.
Apply a zone 4 fault (reverse fault) while the binary inputs BI1, BI2 and BI3 are energized, and
check that the binary output relay BO13 remains operated when the binary input BI4 is
de-energized.
Check that the indications and recordings are correct.
BOP tripping
Set the scheme switch [SCHEME] to "BOP".
Check that the binary input BI4 is de-energized and apply a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Energize the binary input BI4 to simulate trip block signal reception and apply a zone 2 fault.
Check that BOP tripping does not occur.
Apply a zone 2 fault, and check that binary output relay BO13 does not operate. Apply a zone 4
fault (reverse fault), and check that BO13 operates.
Check that the indications and recordings are correct.
SOTF tripping
SOTF tripping is carried out by distance measuring element Z1 to Z4 operation or overcurrent
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......