77
⎯
6 F 2 S 0 8 4 6
Setting
The table shows the setting elements necessary for the overvoltage protection and their setting
ranges.
Element Range
Step Default Remarks
OVS1
5.0 – 150.0 V
0.1 V
120.0 V
OVS1 threshold setting.
TOS1I
0.05 – 100.00
0.01
10.00
OVS1 time multiplier setting. Required if [OVS1EN] = IDMT.
TOS1
0.00 – 300.00 s
0.01 s
0.10 s
OVS1 definite time setting. Required if [OVS1EN] = DT.
TOS1R
0.0 – 300.0 s
0.1 s
0.0 s
OVS1 definite time delayed reset.
OS1DP
10 – 98 %
1 %
95 %
OVS1 DO/PU ratio setting.
OVS2
5.0 – 150.0 V
0.1 V
140.0 V
OVS2 threshold setting.
TOS2
0.00 – 300.00 s
0.01 s
0.10 s
OVS2 definite time setting.
OS2DP
10 - 98 %
1 %
95 %
OVS2 DO/PU ratio setting.
OVG1
5.0 – 150.0 V
0.1V
70.0 V
OVG1 threshold setting.
TOG1I
0.05 – 100.00
0.01
10.00
OVG1 time multiplier setting. Required if [OVG1EN]=IDMT.
TOG1
0.00 – 300.00 s
0.01 s
0.10 s
OVG1 definite time setting. Required if [ZOV1EN]=DT.
TOG1R
0.0 – 300.0 s
0.1 s
0.0 s
OVG1 definite time delayed reset.
OG1DP
10 – 98 %
1 %
95 %
OVG1 DO/PU ratio
OVG2
5.0 – 150.0 V
0.1V
80.0 V
OVG2 threshold setting
TOG2
0.00 – 300.00 s
0.01 s
0.10 s
OVG2 definite time setting
OG2DP
10 – 98 %
1 %
95 %
OVG2 DO/PU ratio
[OVS1EN] Off / DT / IDMT
Off
OVS1 Enable
[OVS2EN] Off / On
Off
OVS2 Enable
[OVG1EN] Off / DT / IDMT
Off
OVG1 Enable
[OVG2EN] Off / On
Off
OVG2 Enable
2.4.9.2 Undervoltage Protection
GRZ100 provides four independent undervoltage elements for phase and earth fault protection.
UVS1 and UVS2 are used for phase fault protection, and UVG1 and UVG2 for earth fault
protection. UVS1 and UVG1 are programmable for inverse time (IDMT) or definite time (DT)
operation. UVS2 and UVG2 have definite time characteristic only.
The UVS1 and UVG1 undervoltage protection elements have an IDMT characteristic defined by
equation (2):
( )
⎥
⎥
⎥
⎦
⎤
⎢
⎢
⎢
⎣
⎡
−
×
=
Vs
V
TMS
t
1
1
(2)
where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = undervoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.4.9.6.
The UVS2 and UVG2 elements are used for definite time undervoltage protection.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......