354
⎯
6
F
2
S
0
8
4
6
6. Default setting
Relay and protection scheme setting sheet
User
NO-ARC,NO-FD
1CB-ARC,NO-FD
2CB-ARC,NO-FD
1CB-ARC,FD
2CB-ARC,FD
1CB-ARC,NO-FD
Setting
5A rating
1A rating
Relay model
101
102
201
202
203
301
302
303
401
501
204
205
206
1
Active group
1 - 8
-
Active setting group
1
1
2
Line name
Specified by user
-
Line name
Specified by user
Specified by user
3
VT
1 -
20000
-
VT ratio
2000
2000
4
VTs1
1 -
20000
-
VT ratio
--
2000
2000
5
VTs2
1 -
20000
-
VT ratio
--
2000
--
2000
--
6
CT
1 -
20000
-
CT ratio
400
400
7
X1
0.00 - 199.99
0.0 - 999.9
Ω
Fault location
2.00 / 10.0
2.00 / 10.0
8
X0
0.00 - 199.99
0.0 - 999.9
Ω
ditto
6.80 / 34.0
6.80 / 34.0
9
X0m
0.00 - 199.99
0.0 - 999.9
Ω
ditto
2.00 / 10.0
2.00 / 10.0
10
R1
0.00 - 199.99
0.0 - 999.9
Ω
ditto
0.20 / 1.0
0.20 / 1.0
11
R0
0.00 - 199.99
0.0 - 999.9
Ω
ditto
0.70 / 3.5
0.70 / 3.5
12
R0m
0.00 - 199.99
0.0 - 999.9
Ω
ditto
0.20 / 1.0
0.20 / 1.0
13
Z0B-L
0.00 - 199.99
0.0 - 999.9
Ω
ditto
2.00 / 10.0
2.00 / 10.0
14
Z0B-R
0.00 - 199.99
0.0 - 999.9
Ω
ditto
2.00 / 10.0
2.00 / 10.0
15
Kab
80 - 120
% ditto
100
100
16
Kbc
80 - 120
% ditto
100
100
17
Kca
80 - 120
% ditto
100
100
18
Ka
80 - 120
% ditto
100
100
19
Kb
80 - 120
% ditto
100
100
20
Kc
80 - 120
% ditto
100
100
21
Line
0.0 - 399.9
km ditto
50.0
50.0
22 Protection scheme
3ZONE - Z1-EXT - PUP - POP -
UOP - BOP - POP+DEF -
UOP+DEF - BOP+DEF - PUP+DEF
-
Protection scheme selection
POP
POP
23
ZS-C
Mho - Quad
-
ZS relay characteristic
Mho
Mho
24
ZG-C
Mho - Quad
-
ZG relay characteristic
Mho
Mho
25
BLZONE
COM - IND
-
Blinder setting mode
COM
COM
26
Z1CNT
1 - 2 - 3 - 4 - 5
-
Z1 trip mode
1
1
27
TPMODE
3PH - 1PH
-
Trip mode
1PH
--
--
28
PSB-Z1
Off - On
-
PSB for Z1 element
On
On
29
PSB-Z1X
Off - On
-
PSB for Z1X element
On
On
30
PSB-Z2
Off - On
-
PSB for Z2 element
On
On
31
PSB-Z3
Off - On
-
PSB for Z3 element
Off
Off
32
PSB-CR
Off - On
-
PSB for carrier trip
On
On
33
PSB-ZF
Off - On
-
PSB for ZF element
Off
Off
34
PSB-ZR1
Off - On
-
PSB for ZR1 element
Off
Off
35
PSB-ZR2
Off - On
-
PSB for ZR2 element
Off
Off
36
PSB-TP
Off - On
-
Trip for under PSB
On
On
37
UVPWIEN
Off - On
-
Countermeasure for lead phase
overreaching
Off
Off
38
STUB
Off - On
-
Stub protection
Off
Off
39
SOTF-DL
CB - UV - Both
-
SOTF condition judged
CB
CB
40
SOTF-OC
Off - On
-
SOTF OC trip
On
On
41
SOTF-Z1
Off - On
-
SOTF Zone1 trip
Off
Off
42
SOTF-Z2
Off - On
-
SOTF Zone2 trip
Off
Off
43
SOTF-Z3
Off - On
-
SOTF Zone3 trip
Off
Off
44
SOTF-F
Off - On
-
SOTF Zone-F trip
Off
Off
45
SOTF-R1
Off - On
-
SOTF Zone-R1 trip
Off
Off
46
SOTF-R2
Off - On
-
SOTF Zone-R2 trip
Off
Off
47
SOTF-ND
Off - On
-
SOTF Zone-ND trip
Off
Off
48
ZFBT
Off - On
-
ZF element back-up trip
Off
Off
49
ZR1BT
Off - On
-
ZR1 element back-up trip
Off
Off
50
ZR2BT
Off - On
-
ZR2 element back-up trip
Off
Off
51
ZNDBT
Off - On
-
Non-directional zone back-up trip
Off
Off
52
OCBT
Off - On
-
OC back-up trip
On
On
53
OCIBT
Off - On
-
OCI back-up trip
On
On
54
MOCI
Long - Std - Very - Ext
-
OCI back-up trip
Std
Std
55
EFBT
Off - On
-
EF back-up trip
On
On
56
EFBTAL
Off - On
-
EF back-up trip alarm
On
On
57 DEF
DEFFEN
Off - On
-
Forward DEF back-up trip enable
Off
Off
58 BU-trip
DEFREN
Off - On
-
Reverse DEF back-up trip enable
Off
Off
59
DEFBTAL
Off - On
-
DEF back-up trip alarm
On
On
60
DEFI
Off - NOD - F - R
-
DEF back-up trip alarm
Off
Off
61
MEFI
Long - Std - Very - Ext
-
EFI back-up trip
Std
Std
62 OVS
OVS1EN
Off - DT - IDMT
-
OVS1 enable
Off
Off
63
OVS2EN
Off - On
-
OVS2 enable
Off
Off
64 OVG
OVG1EN
Off - DT - IDMT
-
OVG1 enable
Off
Off
65
OVG2EN
Off - On
-
OVG2 enable
Off
Off
66 UVS
UVS1EN
Off - DT - IDMT
-
UVS1 enable
Off
Off
67
UVS2EN
Off - On
-
UVS2 enable
Off
Off
68 UVG
UVG1EN
Off - DT - IDMT
-
UVG1 enable
Off
Off
№
Name
Default Setting of Relay Series(5A rating / 1A rating)
Range
Units
Contents
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......