Relay and protection scheme setting sheet
User
NO-ARC,NO-FD
1CB-ARC,NO-FD
2CB-ARC,NO-FD
1CB-ARC,FD
2CB-ARC,FD
1CB-ARC,NO-FD
Setting
5A rating
1A rating
Relay model
101
102
201
202
203
301
302
303
401
501
204
205
206
264
TDEFF
0.00 - 0.30
s
DEF carrier trip delay timer
0.15
0.15
265
TDEFR
0.00 - 0.30
s
ditto
0.15
0.15
266
TCHD
0 - 50
ms Coordination timer
12
12
267
TREBK
0.00 - 10.00
s
Current reverse blocking time
0.10
0.10
268
TECCB
0.00 - 200.00
s
Echo enable timer from CB open
0.10
0.10
269
TSBCT
0.00 - 1.00
s
SBCNT timer
0.10
0.10
270 Autoreclose mode
(Off) - Disable - SPAR - TPAR -
SPAR&TPAR - EXT1P - EXT3P
-
Autoreclosing mode
--
SPAR&TPAR
SPAR&TPAR
271
ARC-CB
ONE - O1 - O2 - L1 - L2
-
ARC mode for 1.5CB system
--
--
L1
--
L1
--
272
ARC-EXT
Off - On
-
ARC initiated by ext. trip
--
Off
Off
273
ARC-DEF
Off - On
-
ARC by DG carr. trip
--
Off
Off
274
ARC-BU
Off - On
-
ARC by back-up trip
--
Off
Off
275
1CB
Off - LB - DB - SY
--
LB
--
LB
--
LB
276
2CB
Off - LB1 - LB2 - DB - SY
--
--
LB1
--
LB1
--
277
ARC-SM
Off - S2 - S3 - S4
-
Multi. shot ARC mode
--
Off
Off
278
ARC-SUC
Off - On
-
ARC success reset
--
Off
Off
279
VTPHSEL
A - B - C
-
VT phase selection
--
A
A
280
VT-RATE
PH/G - PH/PH
-
VT rating
--
PH/G
PH/G
281
3PH-VT
Bus - Line
-
3ph. VT location
--
Line
Line
282
UARCSW
P1 - P2 - P3
-
User ARC switch
--
P1
P1
283
TEVLV
0.01 - 10.00
s
Dead timer reset timing
--
0.30
0.30
284
TRDY1
5 - 300
s
Reclaim timer
--
60
60
285
TSPR1
0.01 - 10.00
s
SPAR dead line timer
--
0.80
0.80
286
TTPR1
0.01 - 100.00
s
TPAR dead line timer
--
0.60
0.60
287
TRR
0.01 - 100.00
s
ARC reset timer
--
2.00
2.00
288
TW1
0.1 - 10.0
s
ARC output pulse timer
--
0.2
0.2
289
TRDY2
5 - 300
s
Reclaim timer
--
--
60
--
60
--
290
TSPR2
0.01 - 10.00
s
SPAR dead line timer
--
--
0.80
--
0.80
--
291
TTPR2
0.1 - 10.0
s
ARC timing for follower CB
--
--
0.1
--
0.1
--
292
TW2
0.1 - 10.0
s
ARC reset timer
--
--
0.2
--
0.2
--
293
TS2
5.0 - 300.0
s
Multi. shot dead timer
--
20.0
20.0
294
TS2R
5.0 - 300.0
s
Multi. shot reset timer
--
30.0
30.0
295
TS3
5.0 - 300.0
s
Multi. shot dead timer
--
20.0
20.0
296
TS3R
5.0 - 300.0
s
Multi. shot reset timer
--
30.0
30.0
297
TS4
5.0 - 300.0
s
Multi. shot dead timer
--
20.0
20.0
298
TS4R
5.0 - 300.0
s
Multi. shot reset timer
--
30.0
30.0
299
TSUC
0.1 - 10.0
s
ARC success reset timer
--
3.0
3.0
300
OVB
10 - 150
V OV element
--
51
51
301
UVB
10 - 150
V UV element
--
13
13
302
OVL1
10 - 150
V OV element
--
51
51
303
UVL1
10 - 150
V UV element
--
13
13
304 SYN1
SY1UV
10 - 150
V Synchro. check (UV)
--
83
83
305
SY1OV
10 - 150
V Synchro. check (OV)
--
51
51
306
SY1
θ
5 - 75
deg Synchro. check (ph. diff.)
--
30
30
307
TSYN1
0.01 - 10.00
s
Synchronism check timer
--
1.00
1.00
308
TDBL1
0.01 - 1.00
s
Voltage check timer
--
0.05
0.05
309
TLBD1
0.01 - 1.00
s
Voltage check timer
--
0.05
0.05
310
T3PLL
0.01 - 1.00
s
three phase live line check timer
--
0.05
0.05
311
OVL2
10 - 150
V OV element
--
--
51
--
51
--
312
UVL2
10 - 150
V UV element
--
--
13
--
13
--
313 SYN2
SY2UV
10 - 150
V Synchro. check (UV)
--
--
83
--
83
--
314
SY2OV
10 - 150
V Synchro. check (OV)
--
--
51
--
51
--
315
SY2
θ
5 - 75
deg Synchro. check (ph. diff.)
--
--
30
--
30
--
316
TSYN2
0.01 - 10.00
s
Synchronism check timer
--
--
1.00
--
1.00
--
317
TDBL2
0.01 - 1.00
s
Voltage check timer
--
--
0.05
--
0.05
--
318
TLBD2
0.01 - 1.00
s
Voltage check timer
--
--
0.05
--
0.05
--
319
BISW1
Norm - Inv
-
Binary input
Norm
Norm
320
BISW2
Norm - Inv
-
ditto
Norm
Norm
321
BISW3
Norm - Inv
-
ditto
Norm
Norm
322
BISW4
Norm - Inv
-
ditto
Norm
Norm
323
BISW5
Norm - Inv
-
ditto
Norm
Norm
324
BISW6
Norm - Inv
-
ditto
Norm
Norm
325
BISW7
Norm - Inv
-
ditto
Norm
Inv
326
BISW8
Norm - Inv
-
ditto
Norm
Inv
327
BISW9
Norm - Inv
-
ditto
Norm
Norm
328
BISW10
Norm - Inv
-
ditto
Norm
Norm
329
BISW11
Norm - Inv
-
ditto
Norm
Norm
330
BISW12
Norm - Inv
-
ditto
Norm
Norm
VCHK
-
TPAR condition
№
Name
Default Setting of Relay Series(5A rating / 1A rating)
Range
Units
Contents
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......