420
⎯
6
F
2
S
0
8
4
6
List of Information
IEC103 Configurator Default setting
INF
Description
Contents
GI Type
COT
FUN
DPI
ID
Signal No.
OFF ON
Standard Information numbers in monitor direction
System Function
0 End of General Interrogation
Transmission completion of GI items.
--
8
10
255
--
--
--
0 Time Synchronization
Time Synchronization ACK.
--
6
8
255
--
--
--
2 Reset FCB
Reset FCB(toggle bit) ACK
--
5
3
128
--
--
--
3 Reset CU
Reset CU ACK
--
5
4
128
--
--
--
4 Start/Restart
Relay start/restart
--
5
5
128
--
--
--
5 Power On
Relay power on.
Not supported
--
--
--
Status Indications
16 Auto-recloser active
If it is possible to use auto-recloser, this item is set
active, if impossible, inactive.
GI
1
1, 9, 11, 12
128
1411
1
2
17 Teleprotection active
If protection using telecommunication is available,
this item is set to active. If not, set to inactive.
GI
1
1, 9, 12
128
1412
1
2
18 Protection active
If the protection is available, this item is set to
active. If not, set to inactive.
GI
1
1, 9, 12
128
1413
1
2
19 LED reset
Reset of latched LEDs
--
1
1, 11, 12
128
1409
--
2
20 Monitor direction blocked
Block the 103 transmission from a relay to control
system. IECBLK: "Blocked" settimg.
GI
1
9, 11
128
1241
1
2
21 Test mode
Transmission of testmode situation froma relay to
control system. IECTST "ON" setting.
GI
1
9, 11
128
1242
1
2
22 Local parameter Setting
When a setting change has done at the local, the
event is sent to control system.
Not supported
23 Characteristic1
Setting group 1 active
GI
1
1, 9, 11, 12
128
1243
1
2
24 Characteristic2
Setting group 2 active
GI
1
1, 9, 11, 12
128
1244
1
2
25 Characteristic3
Setting group 3 active
GI
1
1, 9, 11, 12
128
1245
1
2
26 Characteristic4
Setting group 4 active
GI
1
1, 9, 11, 12
128
1246
1
2
27 Auxiliary input1
Binary input 1
No set
28 Auxiliary input2
Binary input 2
No set
29 Auxiliary input3
Binary input 3
No set
30 Auxiliary input4
Binary input 4
No set
Supervision Indications
32 Measurand supervision I
Zero sequence current supervision
GI
1
1, 9
128
1267
1
2
33 Measurand supervision V
Zero sequence voltage supervision
GI
1
1, 9
128
1268
1
2
35 Phase sequence supervision Negative sequence voltage supevision
GI
1
1, 9
128
1269
1
2
36 Trip circuit supervision
Output circuit supervision
Not supported
37 I>>backup operation
Not supported
38 VT fuse failure
VT failure
GI
1
1, 9
128
172
1
2
39 Teleprotection disturbed
CF(Communication system Fail) supervision
GI
1
1, 9
128
253
1
2
46 Group warning
Only alarming
GI
1
1, 9
128
1258
1
2
47 Group alarm
Trip blocking and alarming
GI
1
1, 9
128
1252
1
2
Earth Fault Indications
48 Earth Fault L1
A phase earth fault
No set
49 Earth Fault L2
B phase earth fault
No set
50 Earth Fault L3
C phase earth fault
No set
51 Earth Fault Fwd
Earth fault forward
Not supported
52 Earth Fault Rev
Earth fault reverse
Not supported
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...