98
⎯
6 F 2 S 0 8 4 6
Figure 2.4.16.2 FD Module
•
Short-circuit the pins 1-2 (located topmost) for the J1 to disable the OCMF.
Short-circuit the pins 3-4 (located second from the top) for the J1 to disable the OCDF.
•
Short-circuit the pins 3-4 for the J2 to energize the output auxiliary relay FD2 only by
the OCMF.
•
Short-circuit the pins 5-6 (located second from the bottom) and open-circuit the pins 7-8
(located bottom) to change the EFF operating threshold level to 15% of the rated
current.
Short-circuit pins 7-8 and open-circuit pins 5-6 to change the EFF operating threshold
level to 20% of rated current.
In other cases, the nominal operating threshold level (10% of the rated current) is kept.
Short-circuit both of the pins 5 - 6 and 7 - 8 to disable the EFF.
•
The pins 1-2 for the J2 is used to set the rated frequency. It is fixed before shipping.
Caution:
Do not change the pins 1-2 for the J2.
Pairs of pins for J1
Pairs of pins for J2
Element Setting
1 - 2
3 - 4
5 - 6
7 - 8
1 - 2
3 - 4
OCMF Enabled Open
Disabled Short
OCDF Enabled
Open
Disabled
Short
EFF Disabled
Short
Short
10% of rated current
Open
Open
15% of rated current
Short
Open
20% of rated current
Open
Short
FD 50Hz
rating
Open
60Hz
rating
Short
FD2 Normal Open
Only
OCMF Short
All the FD elements retain the nominal operating threshold when none of the paired pins are
Lever
Connector
plug
Ribbon cable
receptacle
Four pairs of pins
Rear
Front
J1
2
1
8
7
J2
8
7
1
2
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......