118
⎯
6 F 2 S 0 8 4 6
Figure 2.5.10.2 OCMF Output Logic
Current change detection element OCDF
The characteristic of the OCDF is same as the OCD element, see Section 2.5.7.
Undervoltage change detection element UVDF
The UVDF operates if a voltage drops by 7 percent compared to that of one cycle before.
Therefore, the operating sensitivity of this element is related not to the rated voltage but to the
running voltage.
The following are the level detectors and the operation decision is made by comparing the current
or voltage amplitude with the relevant setting.
Earth fault overcurrent element EFF
The EFF measures the residual current and its detecting level is fixed at 10% of the rated current.
Undervoltage element UVSF and UVGF
The UVSF measures a phase-to-phase voltage while the UVGF measures a phase-to-earth voltage.
Their detecting level is fixed at 80V and 46V, respectively. However, in case of fault with more
than 80V, the undervoltage change detection element UVDF detects the fault.
≥
1
LD1
5s
&
LD2
Single Shot
OCMF
Output
5s
•
•
•
•
•
•
•
•
•
&
LD7
5s
&
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......