191
⎯
6 F 2 S 0 8 4 6
If 4 (= Setting (change)) is entered on the top "MENU" screen, the password trap screen
"Password" is displayed. If the password is not entered correctly, it is not possible to move to the
"Setting (change)" sub-menu screens.
P a s s w o r d
I n p u t
p a s s w o r d
[
]
Canceling or changing the password
To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The
"Setting (change)" screen is then displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
If you forget the password
Press CANCEL and RESET keys together for one second on the top "MENU" screen. The
screen goes off, and the password protection of the GRZ100 is canceled. Set the password again.
4.2.6.3 Description
To enter the plant name and other data, do the following. These data are attached to records.
•
Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
•
Press 2 (= Description) to display the "Description" screen.
/ 2
D e s c r i p t i o n
1 = P l a n
n a
t
e
= D e
i
2
s c r i
t
p
m
o n
•
To enter the plant name, select 1 (= Plant name) on the "Description" screen.
/ 3
P l a n t
n a m e
]
_
[
→
←
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
( ) [ ] @ _
a b c d e f g h i j k l m n o p q r s t u v w x y z
{ } * / + - < = >
0 1 2 3 4 5 6 7 8 9
! ”# $ % & ’:;,.^ `
→
←
→
←
To enter special items, select 2 (= Description) on the "Description" screen.
/ 3
D e s c r
p t i o
]
_
[
→
←
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
( ) [ ] @
a b c d e f g h i j k l m n o p q r s t u v w x y z
{ } * / + - < = >
0 1 2 3 4 5 6 7 8 9
!
”
# $ % &
’
:;,.^ `
→
←
→
←
i
n
•
Enter the text string.
The plant name and special items entered are viewed with the "Setting (view)" sub-menu and
attached to disturbance records when they are displayed on a local or a remote PC.
4.2.6.4 Communication
If the relay is linked with RSM (relay setting and monitoring system) or IEC60870-5-103, the
relay address must be set. Do this as follows:
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......