Connect a phase angle meter to the three-phase voltages taking the scheme switch [VT-RATE]
and [VTPHSEL] setting into consideration. The phase angle meter connection shown in Figure
6.5.1.7 is the case for the default settings, that is, [VT-RATE] and [VTPHSEL] are set to "PH/G"
and "A" respectively.
[VT-RATE] setting
[VTPH-SEL] setting
Meter connection phase
PH/G A
A-N
B B-N
C C-N
PH/PH A
A-B
B B-C
C C-A
Voltage check element OVB, UVB, OVL1, UVL1, OVL2, and UVL2
•
Press 5 (= Logic circuit) on the "Test" screen to display the Logic circuit screen.
•
Enter a signal number for TermA line to observe at monitoring jack A and press the ENTER
key.
•
Apply three-phase rated voltage and single-phase rated voltage as shown in Figure 6.5.1.7.
OVB and UVB :
•
Change the magnitude of the three-phase voltage if the scheme switch [3PH-VT] is set to
"Bus" or adjust the magnitude of the single-phase voltage if it is set to "Line". Measure the
value at which the element operates and check that it is within
±
5% of the setting.
OVL1 and UVL1 :
•
Adjust the magnitude of the single-phase voltage if the scheme switch [3PH-VT] is set to
"Bus"; adjust the magnitude of the three-phase voltage if the scheme switch [3PH-VT] is set to
"Line". Measure the value at which the element operates and check that it is within
±
5% of the
setting.
OVL2 and UVL2 :
•
Adjust the magnitude of voltage applied to terminal 17 and 18 and measure the value at which
the element operates. Check that the measured value is within
±
5% of the setting.
Synchronism check element SYN1
•
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
•
Enter a signal number for TermA line to observe at monitoring jack A and press the ENTER
key.
•
Apply a three-phase rated voltage and a single-phase rated voltage as shown Figure 6.5.1.7.
Voltage check:
•
Set the three-phase voltage to any value over the SY1OV setting. (The default setting of
SY1OV is 51 V.)
Whilst keeping Vs1 in-phase with Va, increase the single-phase voltage Vs1 from zero volt.
Measure the voltage at which the element operates. Check that the measured voltage is within
±
5% of the SY1UV setting.
•
Further increase Vs1 and measure the voltage at that the element resets. Check that the
measured voltage is within
±
5% of the SY1OV setting.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......