2.5.10 Fault Detector Elements
The fault detector incorporates the following six fault detection elements.
Multi-level overcurrent element OCMF
The OCMF is used as a fault detector for the out-of-step protection.
The current fluctuates in an out-of-step situation. To detect this current securely, the OCMF has
seven current level detectors. Each current level detector LD1 to LD7 operates when the current
exceeds each setting L1 to L7 and resets when the current falls below 80 % of the setting. The
settings are fixed as shown in Table 2.5.10.1 as a ratio to the rated current In.
Table 2.5.10.1 Level Detector Settings
Detector Operate
Reset
LD1
0.10
×
In 0.08
×
In
LD2
0.16
×
In 0.13
×
In
LD3
0.26
×
In 0.21
×
In
LD4
0.41
×
In 0.33
×
In
LD5
0.66
×
In 0.53
×
In
LD6
1.05
×
In 0.84
×
In
LD7
1.68
×
In 1.34
×
In
(In:
Rated
current)
Figure 2.5.10.1 shows the characteristics of the OCMF element.
L1 L2
I
0
L7
L6
L5
L4
L3
D.O./P.U.=0.8
Figure 2.5.10.1 OCMF Element
Figure 2.5.10.2 shows the OCMF output logic. The OCMF operates and keeps operating for five
seconds when any of the level detectors operate and reset without time delay when all of the level
detectors reset.
The level detection is performed for phase-to-phase current on A- and B-phase.
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......