407
⎯
6
F
2
S
0
8
4
6
Therefore, load current IL is:
IL = (Source voltage)/(A s/s back imp Line imp B s/s impedance)
=
(150kV/ 3 )/(0.94
×
75 + 16.8
×
(0.0197
2
+ 0.2747
2
) + 0.94
×
75)
=
594.7A
3.2
Minimum fault current
The minimum fault current Ifmin on a protected transmission line is the current of the phase to
earth fault on the nearest remote terminal.
To calculate Ifmin, zero sequence earth fault current (Io), positive sequence earth fault current
(I1) and negative earth fault current (I2) are calculated as follows:
I0 = I1 = I2 = (Source voltage)/{(Back impedance of A s/s)
+ (Transmission line zero sequence impedance)
+ (Transmission line positive sequence impedance)
×
2*}
=
(150kV/ 3 )/{(0.94
×
75) + 16.8
×
(0.4970
2
+ 1.4387
2
)
+
2
×
16.8
×
(0.0197
2
+ 0.2747
2
) }
=
822.28A
So,
Ifmin= I0 + I1+ I2 = 3
×
822.28 = 2.47kA
*Note:
Assuming that positive sequence impedance = negative sequence impedance.
B s/s
Line length: 16.8km
A s/s
M
Earth fault
GRZ100
Summary of Contents for GRZ100 B Series
Page 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Page 271: ... 270 6 F 2 S 0 8 4 6 ...
Page 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Page 307: ... 306 6 F 2 S 0 8 4 6 ...
Page 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Page 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Page 321: ... 320 6 F 2 S 0 8 4 6 ...
Page 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Page 331: ... 330 6 F 2 S 0 8 4 6 ...
Page 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Page 377: ... 376 6 F 2 S 0 8 4 6 ...
Page 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Page 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 389: ... 388 6 F 2 S 0 8 4 6 ...
Page 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Page 401: ... 400 6 F 2 S 0 8 4 6 ...
Page 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Page 405: ... 404 6 F 2 S 0 8 4 6 ...
Page 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Page 417: ... 416 6 F 2 S 0 8 4 6 ...
Page 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Page 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Page 437: ... 436 6 F 2 S 0 8 4 6 ...
Page 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Page 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Page 447: ......