Digital Phase 
Failure and  
Phase Sequence
Device

ke-FKR4 (D)

Phase Sequence Control

 Over Voltage Protection

Under Voltage Protection

Unbalanced Voltage  
Protection

Over Frequency 
Protection

Under Frequency 
Protection

TRUE RMS

Latch Function

V

L1

,

V

L2,

V

L3

V

L12,

V

L23,

V

L13

General

In three phase systems, it measures  
RMS values of AC voltages and system
frequency sensitively. Using up direction 
button (Select) phase-neutral voltages and
phase-phase voltages monitor sequentially
ke-FKR4(D) has many  features. 
Those are;
- Phase Failure
- Phase Sequence 
- Over Voltage Protection
- Under Voltage Protection
- Voltage Unbalance  (asymmetry) 
  Protection
- Over Frequency  Protection
- Under Frequency  Protection

When device is turn on if its adjusted 
voltages and frequency in its interval and  
if phase sequence is correct relay  switch on.
If any of error occurred ( except phase failure
and phase sequence ) at the end of adjusted 
time relay switch off its contact. When system
return normal  values, at the end of time out 
relay switch on.   

L1

L2

L3

Re

< t-3

t-3

Phase Failure:  (u-U)

Before starting system , it controls phase absence then if all phases  exits Normal 
LED turn on and relay  contact  switch on. In case of missing of any L1,L2,L3 
phases , Normal LED turn off  and relay  switch  off its contact .In this case when 
pressing  Reset button, 

u-U 

warn

 

appears

 

on display.

V

L1

Display
Function:

L1 L2 L3

L1 L2 L3

V

L2

L1 L2 L3

V

L3

L1 L2 L3

V

L12

L1 L2 L3

V

L23

L1 L2 L3

V

L13

Select:

(Up direction) when 

pressing continuously,
screen displays  frequency 
of system. When button 
release device continue 
to show voltage. 

IMPORTANT:

  L1 - N  is device supply inputs. Thus,the applied L1 – N voltage 

must be rated voltage of  system . 
The measured frequency also  must the  frequency  of the system.

Voltage Unbalanced:  (unb)

The phase-phase voltage unbalance limit can be adjusted  between(%5-%20) . 
When it exceeds the adjusted limit , the device switched off its out contact 
at the end of  t-1 delay. In this case when pushing Reset button 

unb

 warn  

appear on the screen. For the returning normal state, asymmetry values 
should under % 20 (hysteresis value). In this case at the end of t3 time Normal 
LED turned on and output contact switch  on. If the phase-phase voltage  
unbalance, return adjusted value shorter than  t-1 time, output relay does not  
release its contact. Hysteresis  is %20.

Example: Let's say that asymmetry value is set to 15% for a 3 x 380VAC. 
In this case, relay contact switch off  at (380-(380x0.15))=323 V.
Switch on the contact is performed at 323+(380x15%x20%)= 334V. 
(20% is the hysteresis).

    (V

max 

- V

min

 % un b  =

            x 100      Hys = 380 x (% Asm) x (% 20)

         380

Re

L1,L2,L3

L2,L3

L1
L2
L3

Phase Sequetion:  (Seq)

In case of wrong phase order , Normal LED turned off and relay contact is 
not switch  on. In this case if  Reset button pushes  

seq

 warn displayed. If  

phase order is corrected , Normal LED turned on and out relay switch on.

Hys

+ % unb

V

nom

Hys

Level

Re

- % unb

t-1

< t-1

t-1

L1,L3,L2

L1,L2,L3

t-3

t-3

V

Re

t

t

t-1

(o-U)

(u-U)

t-3

t-1

t-3

Umax

Umin

Under Voltage

Over Voltage 

L1,L2,L3

Normal

Normal

Over and Under Voltage :  (o-U),(u-U)

Under voltage (u-U)   it can adjusted between Umin= (300 – 370 V).
Over voltage    (o-U) it can adjusted between   Umax=(390 – 460 V).
If the voltage drops below the adjusted under voltage limit, when 

u-U 

shows 

on the screen and device switch off its output contact end of the  t-1 time 
Normal LED  turned on .In this case when pushing Reset button 

u-U

 warn 

appear on its  screen.
If the voltage exceed the adjusted over voltage limit, Normal LED turned off 
and output relay switch off. In this case when pushing Reset button 

o-U 

warn 

appers 

on 

its screen.

LOCKING FUNCTION : (LATCH)

It can be controlled by two parameters. Locking time and Locking counter. 
If  the number of opening reaches the adjusted locking counter withing the 
adjusted locking time then device switch off  its contact and locks its 
functions until the user pressed  

Reset 

button. 

If  the locking counter is adjusted to 

oto

 

then this function is disable and 

device never locks itself.

L-t : Locking Time 

( 001 – 060 min. )

It is well know the frequently occurring faults may damage system. For that 
the device when number of faults reaches the adjusted locking number 
within this locking time. This way the system is protected and user has 
chance to investigate the problem. 

L-C : Locking Counter 

( oto , 001 – 010 piece  )

The number of faults allowed within the period L-t. If number of faults 
exceeds this adjusted counter value device locks itself. User must press 
Reset button then the fault passes in order to unlock the device. 
If 

L- C

 is set to 

oto

 then this property  is disabled.  

®