63
Component Names and Functions
Section 2-1
Error Information. Refer to
Inner Board Error Information
For actions required when an error occurs, refer to
Section 11 Troubleshooting
and Maintenance
.
RS-232C Ports
Note
1.
High-speed NT link is only available with Serial Communications Boards/
Units manufactured on or after December 20th, 1999. With earlier models,
only standard NT link is available.
2.
The maximum cable length for RS-232C is 15 m. The RS-232C standard,
however, does not cover baud rates above 19.2 Kbps. Refer to the manual
for the device being connected to confirm support.
Connector Pin Layout
Note
1.
Pin No. 1 and the shell are connected to the ground terminal (GR) of the
Power Supply Unit inside of the Serial Communications Board. Therefore,
the cable shield can be grounded by grounding the GR of the Power Sup-
ply Unit.
2.
The status of the RTS (RS), CTS (CS), DSR (DR), and DTR (ER) signals
can be monitored in the words allocated in the CIO Area. For details, refer
to
2-3 I/O Memory Allocations
.
3.
Pin 6 (5 V) is required when the NT-AL001-E Link Adapter is connected.
For details on connection methods, refer to
Wiring
.
4.
The DSR signal is used to monitor the signal cable. It can also be used as
a CD (carrier detect) signal. (The DSR signal does not affect system oper-
ation, and is available for use by the user.)
Protocol
Host Link
Protocol macro
1:N NT Links
Communications
method
Full-duplex
Full-duplex or half-
duplex
Half-duplex
Synchronization
Start-stop synchronization (asynchronous)
Baud rate
1,200/2,400/4,800/
9,600/19,200/
38,400/57,600/
115,200 bps
1,200/2,400/4,800/
9,600/19,200/
38,400 bps
Standard NT link or
high-speed NT link
Connections
1:1 (1:N is possible using Link Adapters)
Transmission
distance
15 m max. (see note 2)
Interface
Complies with EIA RS-232C
Pin No.
Abbreviation
Signal name
I/O
1 (see note 1)
FG
Shield
---
2
SD
Send data
Output
3
RD
Receive data
Input
4 (see note 2)
RTS (RS)
Request to send
Output
5 (see note 2)
CTS (CS)
Clear to send
Input
6 (see note 3)
5V
Power supply
---
7 (see note 2)
DSR (DR)
Data set ready
Input
8 (see note 2)
DTR (ER)
Data terminal ready (see
note 4)
Output
9
SG
Signal ground
---
Shell (see note 1)
FG
Shield
---
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...