215
Protocol Conversion
Section 6-5
Executing Smart Active Parts Using an NS-series PT (Sending Internal FINS Messages)
The Board/Unit converts the FINS messages to CompoWay/F protocol for
sending in this operation.
Note
(1) The FINS header contains the following information.
• Remote destination network address (DNA)
• With routing tables that treat serial communications path as a network:
Network address corresponding to serial port in the routing tables.
• Without routing tables that treat serial communications path as a net-
work: Network address for specifying actual remote PLC.
• Remote destination node address (DA1)
• With routing tables that treat serial communications path as a network:
00 hex (local PLC’s internal communications) (For serial-to-serial-to-
serial conversion, increment the Host Link unit number by 1.)
• Without routing tables that treat serial communications path as a net-
work: Node address for specifying actual remote PLC (For serial-to-
serial-to-serial conversion, increment the Host Link unit number by 1.)
• Remote destination unit address (DA2)
Unit address of serial port
Access from PT on Ethernet or serial NT Link
Details
Routing tables
to treat serial
communication
s path as
network
Note
When the NS-series PT is connected serially to the
PLC using serial communications mode (1:N NT
Links), and the NS-series PT sends FINS com-
mands encapsulated in NT Link commands using
Smart Active Parts, the CPU Unit removes the NT
Link header, etc. from the received command, con-
verting it to a FINS command, and transfers the
command to the Serial Communications Board/
Unit. The Serial Communications Board/Unit uses
the Serial Gateway to convert the command into
the specified protocol. This operation enables seri-
ally connected devices to access the Serial Com-
munications Board/Unit from Smart Active Parts
using an NS-series PT.
Access via serial communications using
CompoWay/F is possible from a PT con-
nected to the network by executing a
Smart Active Part that is connected seri-
ally, which automatically sends an internal
FINS command.
Optional
NS-series PT
Smart Active Part
FINS header
2803
FINS message (sent internally)
Serial Communications Unit/Board
CPU Unit
RS-485 (CompoWay/F)
Ethernet
CompoWay/F
command
CompoWay/F
command
Protocol
conversion
CompoWay/F-compatible
OMRON component
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...