344
Troubleshooting
Section 11-3
11-3-6 Modbus-RTU Slave Mode
Serial commu-
nications
mode
Indicator
status
Status
information,
etc.
CIO Area
Cause
Remedy
Serial commu-
nications mode
is not set to
Modbus-RTU
slave mode.
---
---
Bits 12 to 15 (Serial
Communications
Mode) of CIO Area
words n + 5/n + 15
are set to a value
other than A Hex.
Serial communica-
tions mode is not
set correctly.
Set bits 08 to 11 (Serial
Communications Mode) of
DM Area words m/m + 10
to A Hex (Modbus-RTU
slave mode).
Serial commu-
nications mode
is set to Mod-
bus-RTU slave
mode.
The SD
@
/RD
@
and COM
@
indicators do
not flash at all.
(Communica-
tions have not
been electri-
cally estab-
lished.)
---
---
Cables are incor-
rectly connected.
The RS-422A/485
port setting (2-wire
or 4-wire) is incor-
rect.
Adapters such as
the NT-AL001-E are
incorrectly wired or
set.
Check the wiring.
Reset the port to the cor-
rect wiring setting.
Wire all nodes using the 4-
wire method.
Commands are not
being set from the
host.
Reset the serial port at the
host, and rewrite the pro-
gram.
This is a hardware
error.
Set bits 08 to 11 (Serial
Communications Mode) of
DM Area words m/m + 10
to F Hex (Loopback Test
Serial Communications
Mode). Then, connect the
connector wire for a loop-
back test and conduct a
loopback test by turning
ON bit 14 (Loopback Test
Switch) of CIO Area word
n. The test data is
reflected in CIO Area
words n+9/n+19. If an
error occurs during the
test, replace the Board or
Unit.
The RD
@
and
COM
@
indica-
tors are flash-
ing, but the
response has
not been
returned from
the host.
For the Unit, the
SD
@
indicator
does not flash
at all (Commu-
nications have
been electri-
cally estab-
lished.)
There is no
transmission
error.
CIO Area words n +
8/n + 18 (transmis-
sion error status)
are set to 0000 Hex.
CIO Area words n +
5/n + 15 (port set-
tings in the System
Setup) do not corre-
spond to the set-
tings of the remote
device.
The System Setup
in DM Area words m
+ 6/m + 16 of the
Board or Unit (Mod-
bus-RTU slave
address) does not
correspond to the
settings for the
remote device.
The command for-
mat and data length
of the data sent
from the host are
incorrect.
Correct the setting in DM
Area words m + 6/m + 16
of the Board or Unit (Mod-
bus slave address) so that
they correspond to the set-
tings at the host device.
Correct the command
frame (destination Mod-
bus slave address) and the
program.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...