132
Communications Timing
Section 4-4
The operation of Host Link communications is not affected by a protocol data
error.
Port Setting Status
The settings in the Setup Area for the following items will be stored: Serial
communications mode, baud rate, start bits, data length, stop bits, parity,
ports, terminating resistance, setup error, and port operating/stopped status.
The port operating/stopped status will always be 1 for Host Link mode.
Communications Status
The flow control and buffer status is stored. These bits are cleared at startup
or when a port is restarted using STUP(237) or a Port Settings Change Bit
(Auxiliary Area).
Transmission Control
Signal Status
The status of the following transmission control signals is stored: ER signal,
DTR signal, CTS signal, and RTS signal. 1: High, 0: Low
Transmission Error Status
The Transmission Error Flag (bit 15) will turn ON if any of the following flags
turn ON: Overrun Error (bit 04), Framing Error (bit 03), or Parity Error (bit 02).
4-4
Communications Timing
This section describes the timing of sending commands and controlling com-
munications in the Host Link mode.
4-4-1
Simultaneous Commands and Communications Ports
The CS/CJ-series CPU Units provide eight logical ports that can be used
when executing SEND(090), RECV(098), and CMND(490). Therefore, up to
eight commands can be executed for one physical port during any one cycle.
The maximum number of messages, however, that can be sent or received in
one CPU Bus Unit service time is two messages from the CPU Unit to the
Board or Unit and two messages from the Board or Unit to the CPU Unit.
Note
1.
If more than eight communications instructions are being used, then exclu-
sive control must be performed to make sure that not more than eight are
executed at the same time. Refer to descriptions of network communica-
tions instructions in the
CS/CJ-series Communications Commands Refer-
ence Manual
(W342).
2.
The same communications port numbers are used by both the communi-
cations instructions (SEND(090), RECV(098), and CMND(490)) and the
PROTOCOL MACRO instruction (PMCR(260)). The same port number
cannot be used by more than one of these instructions at the same time.
Board or Unit
Logical port
CPU Unit
Instruction 1
Instruction 2
Instruction 3
Instruction 4
Instruction 5
Instruction 6
Instruction 7
Instruction 8
One port must be specified for each instruction.
5
1
6
3
7
2
0
4
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...