167
Auxiliary Area and CIO Area Allocations
Section 5-3
Status Area Descriptions
Name
Address
Meaning
Timing
Initialize
ON
OFF
Error log
data error
Board:
CIO 190101
Unit:
n + 1 bit 01
If a write to EEPROM fails for the error log, it
is assumed the EEPROM is beyond its use-
ful life and this flag is turned ON. With a
Serial Communications Unit, the ERC indica-
tor will also light. Although this has no effect
on communications and other functions,
replace the Board or Unit promptly for ease
of maintenance.
Startup
(see note)
At error
Startup
Protocol
data error
Board:
CIO 190100
Unit:
n + 1 bit 00
Board only:
A42409
This flag is turned ON if an error is detected
in the protocol data SUM check when the
power is turned ON. With a Serial Communi-
cations Board, the ERR/ALM indicator on the
CPU Unit will also flash and the RDY indica-
tor will flash at 1-second intervals. A42409
(Board only) of the Auxiliary Area will also
turn ON.
With a Serial Communications Unit, the RDY
and ERC indicator will flash.
This error may occur if the communications
connector becomes disconnected or the
PLC power is turned OFF during protocol
data transfer. Use the CX-Protocol to trans-
fer of the protocol data again.
Startup
(see note)
At error
When pro-
tocol data
has been
success-
fully trans-
ferred
Setup error
Board:
CIO 190601 (port 1)
CIO 191601 (port 2)
Unit:
n + 6 bit 01 (port 1)
n + 16 bit 01 (port 2)
Board only:
A42408 (not avail-
able for Unit)
This flag is turned ON if a Setup error occurs
in the allocated DM Area, After changing the
Setup, turn ON the power again, restart the
Board/Unit, restart the port, or execute the
STUP(237) instruction.
Startup
(see note)
At error
Startup
(see note)
Port operat-
ing
Board:
CIO 190600 (port 1)
CIO 191600 (port 2)
Unit:
n + 6 bit 00 (port 1)
n + 16 bit 00 (port 2)
ON when the port can operate correctly.
OFF when protocol macro data is being
transferred.
Startup
(see note)
At error
After pro-
tocol data
has been
transferred
Remote Unit
receive
busy/receive
wait
Board:
CIO 190710 (port 1)
CIO 191710 (port 2)
Unit:
n + 7 bit 10 (port 1)
n + 17 bit 10 (port 2)
This flag indicates the receive status of a
remote Unit during SEND when Xon/Xoff
flow control or RS/CS flow control is set in
the transmission control parameters. When
Xon/Xoff flow control is set, the reception
buffer is cleared when the sequence starts,
so the status area is set to remote Unit
receive wait (0).
1: Remote Unit receive busy
(Reception is disabled because the
reception buffer is full.)
0: Remote Unit receive wait (Reception is
enabled.)
Startup
(see note)
When sta-
tus is read
After busy
status has
been
released
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...