349
Error Logs
Section 11-4
0014 Hex
Inner bus error
Always 00 Hex
Always 00 Hex
Yes
0108 Hex
Send not possible because
Unit is not detected
Event Send/Receive Errors
Commands:
Send source network address < 80
Bit 15:
OFF
Bits 08 to 14:
Send source network address
Bits 00 to 07:
Send source node address
Send source network address
≥
80
Bit 15:
OFF
Bits 08 to 14:
00
Bits 00 to 07:
Send source network address
Responses:
Send destination network address < 80
Bit 15:
ON
Bits 08 to 14:
Send destination network address
Bits 00 to 07:
Send destination node address
Send destination network address
≥
80
Bit 15:
ON
Bits 08 to 14:
00
Bits 00 to 07:
Send destination network address
No
010B Hex
Send not possible due to
CPU Unit error
No
010D Hex
Send not possible due to
remote address setting error
No
010E Hex
Send not possible because
routing tables are not set
properly
No
0112 Hex
Send not possible due to
header setting error
No
0117 Hex
Internal reception buffer full
No
0118 Hex
Illegal packet discarded
No
011B Hex
Parity error
01 Hex: Port 1
02 Hex: Port 2
Always 00 Hex
No
011C Hex
Framing error
No
011D Hex
Overrun error
No
011E Hex
FCS check error
No
021A Hex
Setting table logic error
Always 00 Hex
03 Hex: Routing tables
05 Hex: CPU Bus Unit/
Inner Board DM Area
No
0300 Hex
Parameter packet discarded Same contents as event send/receive errors.
No
0301 Hex
Protocol macro operation
error
01 Hex: Port 1
02 Hex: Port 2
Protocol macro error code
No
0302 Hex
Illegal protocol packet dis-
carded.
01 Hex: Port 1
02 Hex: Port 2
Always 00 Hex
No
0601 Hex
Board/Unit error
Check the operating environment.
Yes
0602 Hex
CPU Bus Unit/Inner Board
memory error
01 Hex: Read error
02 Hex: Write error
06 Hex: Error log
07 Hex: Protocol data
No
Error code
Error contents
Details
Stored in
EEPROM
First byte
Second byte
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...