![Omron SYSMAC CJ1W-SCU21-V1 Operation Manual Download Page 583](http://html1.mh-extra.com/html/omron/sysmac-cj1w-scu21-v1/sysmac-cj1w-scu21-v1_operation-manual_743586583.webp)
554
E5
@
J Temperature Controller Protocol
Appendix J
Read Output Value (Sequence No. 211 (Hex 00D3))
Reads the output value and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Read Process Value (Sequence No. 212 (Hex 00D4))
Reads the process value and status data and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Read Set Point Limit (Sequence No. 213 (Hex 00D5))
Reads the set point limits and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0002 (fixed)
+1
Unit No. (2 digits BCD)
00 to 31
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0002
+1
Output value
(4 digits BCD)
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0002 (fixed)
+1
Unit No. (2 digits BCD)
00 to 31
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0003
+1
Process value (4 digits BCD)
0000 to 9999
When the left digit is –1, A is set and when it
is –, F is set.
+2
Status data (4 digits Hex)
0000 to 9999
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Receive data
storage words
Number of receive data words
+0
+1
Output value
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Receive data
storage words
Number of receive data words
+0
+1
+2
Process value
Status data
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...