Troubleshooting
Section 11-3
Response Received from Remote Device but Error Remains
Error conditions
Cause
Remedy
Board/Unit
status
Serial com-
munica-
tions mode
Indicator
display
FINS end
code sent
to FINS
transmis-
sion source
Words allo-
cated in
CIO Area
A normal
FINS end
code is
returned
from the
remote
device, but
there is no
response
data after
the end
code.
The serial
communica-
tions mode
is set to
Serial Gate-
way or pro-
tocol macro
mode.
The RD
@/
SD
@
and
COM
@
indi-
cators all
flash.
0000 hex
---
The FINS command
requires a
response, but the
command after con-
version does not
require a response
(e.g., broadcasting)
Check the specifications of
the command to be con-
verted.
A response
was
received
from the
remote
device after
a response
timeout error
was
received for
a converted
command
that was
sent to the
remote
device.
0205 hex
(response
timeout),
etc.
Bit 05 of CIO
word n+8/
n+18 (Serial
Gateway
send start
timeout or
Serial Gate-
way
response
timeout) is
ON.
A Serial Gateway
response timeout
occurred, but the
response data was
received normally
after the timeout.
This is a result of
the Serial Gateway
response timeout
monitoring time set-
ting in DM Area
word m+7/m+17
being too short.
Set a longer time for the
Serial Gateway response
timeout monitoring time in
DM Area word m+7/m+17.
A FINS error
end code
was
returned to
the FINS
transmis-
sion source.
0206 hex
(transmis-
sion error)
CIO word
n+8/n+18 bit
07 (FCS
check error)
or bit 02
(parity error)
is ON.
Either of the follow-
ing errors occurred
in the protocol after
conversion.
Conversion to Com-
poWay/F com-
mand: BCC error or
parity error
Conversion to Mod-
bus-RTU command:
CRC error or parity
error
Conversion to Mod-
bus-ASCII com-
mand: CRC error or
checksum error
Conversion to Host
Link FINS com-
mand: FCS error or
parity error
Use shielded twisted-pair
cables.
Lay power lines separately
using ducts.
Increase the number of
resends at the FINS trans-
mission source.
Perform communications
retry as required.
Other FINS
error end
code
---
The Serial Gate-
way was executed,
but the FINS error
completion
occurred.
Perform error processing
based on the following
table of FINS end codes.
Summary of Contents for SYSMAC CJ1W-SCU21-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi...
Page 89: ...60 Basic Operating Procedure Section 1 9...
Page 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Page 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Page 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Page 277: ...248 Communications Frames Section 6 8...
Page 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Page 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Page 391: ...362 Introduction Appendix A...
Page 421: ...392 CompoWay F Master Protocol Appendix B...
Page 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Page 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Page 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Page 627: ...598 ES100 Digital Controller Protocol Appendix K...
Page 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Page 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Page 717: ...688 Visual Inspection System Protocol Appendix O...
Page 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Page 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Page 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Page 781: ...752 Revision History...